Calculating Resistor Size
The standard dynamic braking (DB) resistor assemblies are suitable for a wide variety of drive system 
stopping applications. However, when the driven machinery may present an overhauling load or large 
inertia to the drive system, the suitability of the DB resistor assembly should be checked.
The suitability of a DB resistor assembly is determined by analyzing the mechanical system of the driven 
machinery. From the analysis, the following key parameters are computed:
• The peak braking power required during stopping or speed changes (P
i
). The value of P
i
 determines 
the maximum allowable ohmic value of the DB resistor.
• The amount of power that must be absorbed (P
d
) for a given time (t
d
) by the DB resistors during 
stopping or speed changes of the drive. The value of P
d
 and t
d
 determine the required time-current 
characteristic of the DB resistor.
• The calculation of dynamic braking power requires V
db
.
• V
db
 = 850 V for 460 V drives
V
db
 = 375 V for 230 V drives
• The average power that must be dissipated by the DB resistor during an entire cycle of the machine 
(P
a
). The value of P
a
 determines the required continuous current rating of the DB resistor.
The following example illustrates the process:
Given
The application consists of a 5 hp, 460 Vac, 1740 rpm motor (N
base
 = base speed) with a rotor 
inertia of 0.28 lb-ft
2
. The motor is being controlled by an ATV58HU72N4 operating in the constant 
torque mode. The motor is driving a machine with an inertia 10 times that of the motor with no 
interposing gear box. The machine resistive (friction) torque is one-tenth of the rated motor torque 
at full speed. The requirement is to stop in 5 seconds from rated speed at a rate of 2 cycles/minute.
Mechanical System Parameters:
Rated motor torque: T
n
 = (hp x 5250)/N
base
 = (5 x 5250)/1740 = 15.1 lb-ft
Machine cycle time: t
c
 = (60 seconds)/(two operations per minute) = 30 seconds
Machine speed change during deceleration: N
d
 = 1740 rpm - 0 rpm = 1740 rpm
Machine deceleration time: t
d
 = 5 seconds
Mechanical system resistive (friction) torque: T
r
 = (15.1 lb-ft)/10 = 1.51 lb-ft
Mechanical system overhauling torque: T
o
 = 0.00 lb-ft
Mechanical system combined inertia: J
c
 = 0.28 lb-ft
2
 + (10) x 0.28 lb-ft
2
 = 3.08 lb-ft
2
Mechanical system inertial torque for a 5 second deceleration rate (as set by controller 
deceleration ramp): 
T
j
 = Jc x (N
d
)/(308 x (t
d
)) = 3.08 x 1740/(308 x 5) = 3.48 lb-ft
Required braking torque from motor: T
b
 = T
j
 + To - T
r
 = 3.48 + 0.00 - 1.51 = 1.97 lb-ft
NOTE: The required braking torque must not exceed the motor’s ability to produce torque. For 
inertial loads, including those depicted in the above examples, the required braking torque must 
not exceed the torque producing ability of the dynamic braking unit with the recommended braking 
resistor (approximately 1.5 times the motor rated torque for constant torque applications).
For machines that can continuously overhaul the motor, the value of overhauling torque (T
o
) minus 
the resistive torque (T
r
) must not exceed the motor continuous torque rating at any speed.