58 TRX AC Drives
Configurable I/O Functions
©
 2000–2003 Schneider Electric All Rights Reserved
50
09/2003
Drive Address
This parameter is used to set the address when controlling the drive controller by a Modbus device via 
the RS-485 port. The baud rate is selectable as 9600 or 19,200 bits/sec.The range of addresses is 0 to 
31. The factory setting is 0, indicating that the drive controller is not being controlled via the RS-485 port.
Reset Counters
This parameter can be used to reset the watt-hour meter or the run time meter back to zero.
CONFIGURABLE I/O FUNCTIONS
Configurable I/O Functions can be viewed and modified only when the access locking switch on the 
keypad display is in the total unlock position (see page 24). These parameters can be modified only 
when the motor is stopped.
Default I/O Configurations
Selecting a macro-configuration automatically assigns the inputs and outputs to functions suitable for 
the application. The table below shows the drive controller I/O assignment as a function of the macro-
configuration selected.
Assignable I/O Functions
The table below shows the possible I/O assignments for the ATV58 TRX Type H drive controller and the 
optional I/O Extension Cards. Only one I/O extension card or one communication card can be installed 
in the drive.
The following I/O are on the drive controller. 
• Logic Input 1 (LI1) is configured for Run Forward when the drive controller is set for two wire control 
and configured for STOP when the drive controller is set for three wire control.
• Relay Output 1 (R1) is configured as a fault relay (1 N.O. contact and 1 N.C. contact) and cannot be 
re-assigned.
Factory-Configured Functions for the Three Macro-Configurations
Material Handling
[1]
General Use
 Variable Torque
Basic I/O
Logic input LI1
Forward
 Forward
Forward
Logic input LI2
Reverse
 Reverse
Reverse
Logic input LI3
2 preset speeds
 Jog operation
Auto-Manual 
[3]
Logic input LI4
4 preset speeds
Freewheel stop/Run permissive 
[2]
DC injection braking 
[3]
Analog input AI1
Reference summing
Reference summing
Speed reference 1 
[3]
Analog input AI2
Reference summing
Reference summing
Speed reference 2 
[3]
Analog output AO1
Motor frequency
Motor frequency
Motor frequency
Relay R1
Drive fault relay
Drive fault relay
Drive fault relay
Relay R2
Output contactor control
Motor thermal state attained
Frequency reference attained 
[3]
Analog or Digital I/O Extension Cards
Logic input LI5
8 preset speeds
Fault reset
Freewheel stop
Logic input LI6
Fault reset
Current limit
Ramp switching
Analog input AI3 (analog I/O card)
or
Encoder Inputs (digital I/O card)
Summing speed reference
Summing speed reference
PI regulator
Speed regulation
Speed regulation
Speed regulation
Logic output LO
Current threshold attained
Output contactor control
High speed attained
Analog output AO
Motor current
Motor current
Motor current
[1] Factory default setting for 100 hp products and below.
[2] If the Freewheel Stop/Run Permissive function is configured, the drive controller will not start the motor unless the logic input is connected to +24 V.
[3] For 125–500 hp controllers, the factory settings are: 
LI3 = fault reset; LI4 = Not assigned; AI1 = Reference summing; AI2 = Reference summing; R2 = Drive running.