Schneider Electric 58 TRX User Manual

Page of 232
Altivar
®
 
58 TRX AC Drives
Assignment of Logic Inputs (LIx)
©
 2000–2003 Schneider Electric All Rights Reserved
54
09/2003
+/– Speed
This function may also be referred to as the motorized potentiometer 
function. It allows the speed reference to be increased or decreased using 
one or two logic signals, with or without saving the last reference speed. The 
maximum speed is given by the reference applied to the analog inputs. For 
example, connect AI1 to +10 Vdc. To use this function, two or three logic 
inputs must be re-assigned.
This function is appropriate for:
• Applications involving centralized control of a machine composed of 
several sections operating in one direction.
• Controlling a material handling crane operating in two directions with a a 
pendant control station.
Two examples of this function are shown at the left.
Setpoint Memory
This function is associated with the +/– Speed function, and determines 
whether the speed reference level is read and stored upon loss of the Run 
signal or the mains supply. The stored reference is applied to the next Run 
signal. The function may be set to either Yes (store reference signal) or No 
(do not store reference signal).
Preset Speeds
The Preset Speeds function allows switching between 2, 4, or 8 preset 
speeds, and requires 1, 2, or 3 logic inputs respectively. The function is 
typically used with materials handling and machines with several operating 
speeds. A typical example involving four speeds is shown to the left.
In this example, four speeds are obtained with inputs LI3 and LI4. At state 0, 
the speed is LSP or the speed reference depending on the level of analog 
inputs AI1 and AI2. The preset speeds may be adjusted from 0.1 Hz to the 
maximum frequency. The factory default settings are:
• 1st Speed: LSP or reference.
• 2nd Speed: 5 Hz.
• 3rd Speed: 10 Hz.
• 4th Speed: HSP
NOTE:  To reassign the logic inputs to a function other than Preset Speeds, 
PS8 (LIz) must be cleared, then PS4 (LIy), then PS2 (LIx).
Preset Speed Logic
2 Preset Speeds
4 Preset Speeds
8 Preset Speeds
Assign LIx to PS2.
Assign LIx to PS2, then LIy to PS4.
Assign LIx to PS2, then LIy to PS4, then 
LIz to PS8.
LIx
Speed reference
LIy
LIx
Speed reference
LIz
LIy
LIx
Speed reference
0
LSP  +  AI  reference
0
0
LSP  +  AI  reference
0
0
0
LSP  +  AI  reference
1
HSP
0
1
SP2
0
0
1
SP2
1
0
SP3
0
1
0
SP3
1
1
HSP
0
1
1
SP4
1
0
0
SP5
1
0
1
SP6
1
1
0
SP7
1
1
1
HSP
f (Hz)
t
t
t
t
Forward
or
Reverse
+ Speed
d
- Speed
d
1
0
1
0
1
0
Pl
us
Mi
nus
E
x1.e
p
s
a
b
A
B
LI1
LI2
LI3
LI4
+24
AIX
+/- Speed With Saving the Last Reference 
Timing Diagram
+/- Speed Wiring Example
LSP
f (Hz)
Forward
or
Reverse
LI1 1
1
LI3 0
1
LI4 0
LI2 0
PresetSpds.eps
HSP
LI1: Forward
LI2: Reverse
LI3: +Speed
LI4: -Speed
ATV58 TRX terminal
Activate input 
a or b, then 
activate input 
A or B.
Max. speed
Preset Speeds Timing Diagram
+S
p
eed
_-
S
p
ee
d W
ir
ing
 (
c
at
a
lo
g
).
ep
s