58 TRX AC Drives
 Assignment of Analog Outputs (AOx)
63
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
ASSIGNMENT OF ANALOG OUTPUTS (AOx)
The following sections describe the possible assignments of the Analog Outputs (AOx) on the drive 
controller and on the optional Extension Cards. The analog output is a current output. The minimum and 
maximum values are configurable, with a range of 0-20 mA, as shown in the graph to the left.
Motor Current
When configured for motor current, the analog output provides a signal proportional to motor current. 
The minimum configured value corresponds to zero, while the maximum configured value of the analog 
output corresponds to 200% of the drive controller’s constant-torque rating.
Output Frequency
When configured for output frequency, the analog output provides a signal proportional to motor 
frequency estimated by the drive controller. The minimum configured value corresponds to zero, while 
the maximum configured value of the analog output corresponds to the maximum frequency setting, not 
the high speed setting.
Ramp Output
When configured for ramp output, the analog output provides a signal proportional to the frequency the 
drive controller is commanding the motor to run. The minimum configured value corresponds to zero, 
while the maximum configured value of the analog output corresponds to the maximum frequency 
setting, not the high speed setting.
Motor Torque
When configured for motor torque, the analog output provides a signal proportional to motor torque as 
an absolute value. The minimum configured value corresponds to zero, while the maximum configured 
value of the analog output corresponds to 200% of the nominal motor torque.
Signed Motor Torque
When configured for signed motor torque, the analog output provides a signal proportional to motor 
torque and provides an indication of braking torque or motoring torque. The minimum configured value 
corresponds to 200% of the braking torque, while the maximum value of the analog output corresponds 
to 200% of the nominal motor torque. Zero torque corresponds to the average torque value ([minimum 
value + maximum value] divided by 2).
Signed Ramp
When configured for signed ramp output, the analog output provides a signal proportional to the 
frequency the drive controller is commanding the motor to run in the reverse or forward direction. Zero 
frequency corresponds to:
(minimum value + maximum value) / 2.
The minimum configured value corresponds to the maximum frequency in the reverse direction, while 
the maximum configured value corresponds to the maximum frequency in the forward direction. 
PI Setpoint
When configured for PI setpoint, the analog output provides a signal proportional to the PI setpoint being 
provided to the drive controller. The minimum configured value corresponds to the minimum setpoint, 
while the maximum configured value corresponds to the maximum setpoint. 
PI Feedback
When configured for PI feedback, the analog output provides a signal proportional to the PI feedback 
being provided to the drive controller. The minimum configured value corresponds to the minimum 
feedback, while the maximum configured value corresponds to the maximum feedback.
0 mA
4 mA
Minimum
20 mA
20 mA
Maximum
Max.
Min. 
An
O
u
tG
ra
f.e
p
s
Analog Output 
Ranges