Fault Management Parameters
67
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
Automatic Catch of a Spinning Load (Catch-on-the-fly)
This function, also termed a “flying start,” is active by default (although it is automatically disabled if the 
Brake Sequence function is configured). It allows the motor to be restarted without a speed surge after 
one of these events:
• Mains power break or simple switch off.
• Fault reset or automatic restart.
• Freewheel stop or DC injection stop with logic input.
• Momentary loss of power downstream of drive controller. 
On restart, the controller searches for the effective speed of the motor in order to restart on a ramp from 
this speed and return to the reference speed. The speed search time can reach 1 s depending on the 
initial difference.
This function is often used for applications where the motor speed of a machine does not drop rapidly 
after a mains power break (machines with high inertia) as well as fans and pumps driven by residual flux.
Controlled Stop on Power Loss
This function can be used to determine how the drive controller will react to a loss of power. Three 
configurations are possible:
• Disabled.
The drive controller immediately faults in response to an input phase loss. This is the factory setting.
• Follow the programmed deceleration ramp until motor stops or undervoltage fault appears.
Use this configuration if a consistent deceleration ramp is more important than maximizing power 
loss ride through. 
• Maintain DC bus voltage.
With this configuration, DC bus voltage is maintained as long as possible. The ATV58 TRX drive is 
designed to ride through power sags and to provide degraded operation down to 60% of nominal line 
voltage for 500 ms. Longer ride through is possible if there is sufficient kinetic energy generated by 
the connected motor load inertia. An undervoltage fault appears after the voltage drops below 60% 
of nominal line voltage. This configuration should be used to maximize the ride through time of the 
drive controller and to minimize nuisance tripping.