Schneider Electric 58 TRX User Manual

Page of 232
Altivar
®
 
58 TRX AC Drives
Parameter Summary
©
 2000–2003 Schneider Electric All Rights Reserved
74
09/2003
PARAMETER SUMMARY
The following tables show the ATV58 TRX Type H configuration parameters. This page can be copied 
and used as a worksheet to customize settings for your application.   
Adjustment Parameters
Code
Fact. Setting
Cust. Setting
Code
Fact. Setting
Cust. Setting
ACb 
no
SP6 
30 Hz
Hz
ACC 
3 s
s
SP7 
35 Hz
Hz
dEc 
3 s
s
JOG 
10 Hz
Hz
LSP 
0 Hz
Hz
JGt 
0.5 s
s
HSP 
50 / 60 Hz
Hz
brL 
0 Hz
Hz
FLG 
20%
%
Ibr 
0 A
A
StA 
20%
%
brt 
0 s
s
ItH 
0.9 of I
n
A
bEn 
0 Hz
Hz
IdC 
0.7 ItH
A
bEt 
0 s
s
tdC 
0.5 s
s
FFt 
50/60 Hz
Hz
SdC 
Varies
A
rPG 
1
JPF 
0 Hz
Hz
rIG 
1 / s
/ s
JF2 
0 Hz
Hz
PSP 
0.0 s
s
JF3 
0 Hz
Hz
FbS 
0.1
AC2 
5 s
s
PIC 
no
dE2 
5 s
s
PI2 
30%
%
tLS 
no
no  or
s
PI3 
60%
%
USC 
1
dtd 
105%
%
UFr 
100%
%
dtS 
1
SLP 
100% %
Ctd 
1.36 of I
n
A
PFL 
20%
%
ttd 
100%
%
SP2 
10 Hz
Hz
tL2 
200%
%
SP3 
15 Hz
Hz
Ftd 
50/60 Hz
Hz
SP4 
20 Hz
Hz
F2d 
50/60 Hz
Hz
SP5 
25 Hz
Hz
Drive Menu Parameters
Code
Factory Setting
Customer Setting
Code
Factory Setting
Customer Setting
UnS
depends on catalog number
V
Stt
STN
FrS
50 / 60 Hz
Hz
dCF
4
nCr
0.9 of I
n
A
tLI
200%
%
nSP
depends on catalog number
rpm
CLI
1.3 6 of I
n
COS
depends on catalog number
AdC
yes
tUn
no
PCC
1
tFr
60 / 72 Hz
Hz
SFt
LF
nLd
no
SFr
depends on catalog number
kHz
Fdb
no
nrd
yes
Frt
0 Hz
Hz
SPC
no
rPt
LIN
PGt
DET
brA
no
PLS
1024
Command Menu Parameters
Code
Factory Setting
Customer Setting
Code
Factory Setting
Customer Setting
tCC
2 W
AOH
20 mA
mA
tCt
LEL
Str
no
rln
no
LCC
no
bSP
no
PSt
yes
CrL
4 mA
mA
Add
0
CrH
20 mA
mA
tbr
19200
AOL
0 mA
mA
rPr
no