Schneider Electric 58 TRX User Manual

Page of 232
Altivar
®
 
58 TRX AC Drives
Type H Drive Controllers
©
 2000–2003 Schneider Electric All Rights Reserved
8
09/2003
Ratings
ATV58 TRX Type H drive controllers may be rated for constant torque (CT), variable torque (VT), and 
variable torque low noise (VTLN) applications.
• CT applications usually require 100% of motor-rated torque through the entire speed range, high 
transient torque capability, and speed regulation.
• VT applications, such as centrifugal fans and centrifugal pumps, do not require high transient torque 
capability. This typically allows a drive to be rated for additional horsepower and additional current as 
compared to the constant torque rating.
• VTLN applications, such as centrifugal fans and centrifugal pumps, do not require high transient 
torque capability. However, this rating uses a higher switching frequency for quieter motor operation. 
As a result, the drive may be rated at the same horsepower and current as the constant torque rating, 
particularly at large horsepower sizes.
The 125–500 hp drive controllers are listed in this catalog with ratings typically used for VT applications. 
With proper selection, this range of controllers can also be used in CT applications, such as 
compressors, conveyors, and extruders, where high performance is not required at low speeds. The 
125–500 hp product ratings in this catalog are for applications that require 100% rated torque down to 
6 Hz. If the application requires more than 110% transient torque for one minute, select the appropriate 
horsepower product. For assistance with selecting the proper AC drive controller for constant torque 
applications, consult your local Square D drives specialist. 
Application information is also available in product data bulletin SC100, Adjustable Frequency 
Controllers Application Guide
, available at www.SquareD.com, or the NEMA Standards Publication: 
Application Guide For AC Adjustable Speed Drive Systems
Ratings for ATV58 TRX Type H Constant Torque; 208/230 Vac, Single-Phase Input with 3-Phase Output;
Switching Frequency at 4 kHz
Frame Size
Drive Controller 
Catalog Number
Motor Power
208/230 Vac
Rated 
Output Current
Transient 
Output Current
Total Dissipated 
Power at Rated Load
kW
HP
A
A
W
1
ATV58HU09M2ZU
0.37
0.5
2.3
3.1
42
1
ATV58HU18M2ZU
0.75
1
4.1
5.6
64
2
ATV58HU29M2ZU
1.5
2
7.8
10.6
107
2
ATV58HU41M2ZU
2.2
3
11
15.0
156
3
ATV58HU72M2ZU
3
4
13.7
18.6
160
4
ATV58HU90M2ZU
4
5
18.2
24.8
176
4
ATV58HD12M2ZU
5.5
7.5
24.2
32.9
204
Ratings for ATV58 TRX Type H Variable Torque, Low Noise; 208/230 Vac, Single-Phase Input with 3-Phase Output; 
Switching Frequency: ATV58HU09M2–D12M2 at 8 kHz; ATV58HD16M2–D46M2 at 4 KHz
Frame Size
Drive Controller 
Catalog Number
Motor Power
208/230 Vac
Rated 
Output Current
Transient 
Output Current
Total Dissipated 
Power at Rated Load
kW
HP
A
A
W
1
ATV58HU09M2ZU
0.37
0.5
2.5
2.8
42
1
ATV58HU18M2ZU
0.75
1
4.8
5.3
64
2
ATV58HU29M2ZU
1.5
2
7.8
8.6
107
2
ATV58HU41M2ZU
2.2
3
11
12.1
156
3
ATV58HU72M2ZU
3
4
14.3
15.7
160
4
ATV58HU90M2ZU
4
5
17.5
19.3
176
4
ATV58HD12M2ZU
5.5
7.5
25.3
27.8
204
6
ATV58HD16M2XZU
7.5
10
30.8
33.9
323
6
ATV58HD23M2XZU
11
15
46.2
50.8
550
7
ATV58HD28M2XZU
15
20
60
66.0
745
7
ATV58HD33M2XZU
18.5
25
75
82.5
895
7
ATV58HD46M2XZU
22
30
88
96.8
900
Refer to page 127 for a 
complete list of catalog 
numbers. An “X” in the 
catalog number indicates that 
the product does not have an 
internal EMC filter. If an 
internal EMC filter is required, 
delete the “X” from the 
catalog number.
When these drive controllers 
are used with a single-phase 
input, a line reactor (3% 
minimum) must be used.
Refer to page 127 for a 
complete list of catalog 
numbers. An “X” in the 
catalog number indicates that 
the product does not have an 
internal EMC filter. If an 
internal EMC filter is required, 
delete the “X” from the 
catalog number.
When these drive controllers 
are used with a single-phase 
input, a line reactor (3% 
minimum) must be used.