INSTALLATION RECOMMENDATIONS
• The ATV58 TRX drive controller must be installed in a suitable environment. The environment around 
the drive controller must not exceed pollution degree requirements as defined in NEMA ICS-1 
Appendix A or EN60664/IEC60664.
• Install the drive controller vertically (±10°) with the power terminals at the bottom. Avoid placing the 
drive controller near any heat sources.
• Installation of a disconnect switch between the input line and the drive controller should be in 
accordance with national and local codes.
• Overcurrent protection is required. Refer to page 113 for recommended fuses.
• The figure to the left shows the minimum clearances required around each drive controller for 
unobstructed air flow. Also, leave at least 0.4 in. (10 mm) in front of the drive controller. These 
clearances should not be used as minimum enclosure size for proper thermal dissipation.
Depending on the ambient temperatures in which the ATV58 TRX controller is used, the clearance 
on the sides of the controller (dimension d in the drawing), and the particular ATV58 TRX model, 
removal of the protective cover or adding a fan may be required; see the table below for more 
information.
ATV58 TRX Model
Dimension d
Temperature
–10 to +40°C (14 to 104 °F) 40 to 50°C (104 to 122 °F)
50 to 60°C (122 to 140 °F)
HU09M2 to HU72M2
HU18N4 to HU90N4
 50 mm (2 in)
No special precautions needed.
Remove the protective cover 
from the top of the controller 
(see graphic to the left). Degree 
of protection becomes IP20.
Add control card fan kit 
VW3A5882• (see page 33 for 
more information) and derate 
the rated operating current by 
2.2% for each °C over 50 °C.
< 50 mm (2 in)
Remove the protective cover 
from the top of the controller 
(see graphic to the left). Degree 
of protection becomes IP20.
Add control card fan kit 
VW3A5882• (see page 33 for 
more information).
Unacceptable mounting 
clearance.
HU90M2 to HD12M2
HD12N4 to HD23N4
 50 mm (2 in)
No special precautions needed.
Remove the protective cover 
from the drive (see graphic to 
the left). Degree of protection 
becomes IP20. Also derate the 
rated operating current by 2.2% 
for each °C over 40 °C.
Do not install where the ambient 
temperature exceeds 50 °C 
(122 °F).
< 50 mm (2 in)
Remove the protective cover 
from the top of the controller 
(see graphic to the left). Degree 
of protection becomes IP20.
Add control card fan kit 
VW3A5882• (see page 33 for 
more information) and derate 
the rated operating current by 
2.2% for each °C over 40 °C.
Do not install where the ambient 
temperature exceeds 50 °C 
(122 °F).
HD16M2X to HD46M2X
HD28N4 to HD79N4
HD28N4X to HD79N4X
 50 mm (2 in)
No special precautions needed.
Add control card fan kit 
VW3A5882• (see page 33 for 
more information) and derate 
the rated operating current by 
2.2% for each °C over 40 °C.
Do not install where the ambient 
temperature exceeds 50 °C 
(122 °F).
< 50 mm (2 in)
Unacceptable mounting 
clearance.
Unacceptable mounting 
clearance.
Unacceptable mounting 
clearance.
HC10N4X to HC33N4X
< 50 mm (2 in)
No special precautions needed.
Do not install where the ambient 
temperature exceeds 40 °C 
(109 °F).
Do not install where the ambient 
temperature exceeds 50 °C 
(122 °F).
d
d
h
h
Clearances.eps
h = 50 mm (2 in) for:
HU09M2 to HU72M2
HU18N4 to HU90N4
HU90M2 to HD12M2
HD12N4 to HD23N4
h = 100 mm (4 in) for:
HD16M2X to HD46M2X
HD28N4 to HD79N4
HD28N4X to HD79N4X
HC10N4X to HC33N4X
RemoveCvr.eps
Removing the 
Protective Cover
Minimum 
Clearances