Emerson 16E09-101 Installation Instruction

Page of 16
CONTENTS
Basic Description ........................................................   1
Precautions .................................................................   1
Installation ...................................................................   2
Wiring ..........................................................................   3
User Menu ..................................................................   4
Operation ....................................................................   5
Specifications ..............................................................   7
Troubleshooting ...........................................................   8
www.white-rodgers.com
www.emerson.com
PRECAUTIONS 
16E09-101
Universal Electronic Temperature Control
PART NO. 37-6857G
Replaces 37-6857F
1016
INSTALLATION AND
OPERATION INSTRUCTIONS
DESCRIPTION 
The 16E09-101 is a single stage electronic temperature con-
trol, with a Nema 1 rated enclosure, and can be used for most 
applications within the temperature control range of -40° to 
220°F, (-40° to 104°C). The control has an SPDT (Single Pole 
Double Throw) output load relay.
The control has user options to control differential, anti-short 
cycle delay, set back, offset, alarms and more. It includes an 
NTC (Negative Temperature Coefficient) thermistor tempera-
ture sensor, and can be used with certain other NTC or PTC 
(Positive Temperature Coefficient) thermistors that meet the 
specified resistance vs. temperature specifications. See the 
tables on page 7.
The control can fit many applications, which range from 
refrigeration to heating due to the wide temperature range of 
the control stated above. Typical applications include walk-
in freezers, beverage coolers, supermarket display cases 
for flowers, produce, meats, convenience store refrigerated 
cases, food warmers, boiler control, and certain industrial 
applications. 
Save these instructions for future use!
WARNING
!
16E09-101 Optional Accessories / Service Items:
Immerson Well  .................................................... F89-0286
Replacement 7.5' NTC Remote Sensor .............. F136-0114
Well Heat Transfer Compound ............................. F145-0163
  Failure to read and follow all instructions carefully before 
installing or operating this control could cause personal 
injury and/or property damage.
  To  prevent  electrical  shock,  personal  injury  and/or 
equipment damage, disconnect electric power to system 
at main fuse or circuit breaker box prior to installation 
or service.
  To  prevent  scald  injury,  do  not  use  this  control  to 
heat  water  for  bathing,  washing,  hot  tub  or  similar 
applications.
  Where  failure  of  this  control  may  result  in  personal 
injury and/or property damage, additional alarms or limit 
controls must be installed.
  This control is a temperature control and is not to be 
used as a temperature limit control.