Pressure Control
The temperature is controlled by an adjustable pressure 
control located in the machine compartment.  An adjustable 
control has the word COLDER near the knob, with an arrow 
to indicate the adjustment direction.  These controls are 
field adjustable and do not require a service agent.  If you 
have any questions, feel free to contact the Delfield Service 
Department.
The refrigeration systems on self-contained CR & OR models 
were adjusted at the factory to maintain between 36°F and 
40°F.  No adjustment should be necessary.  If adjustment 
does become needed however, the factory recommended 
settings are:
Low-pressure settings (CR models): 82 psi cut-in,               
47 psi cut-out, 35 psi differential.
Low-pressure settings (OR models): 82 psi cut-in,               
40 psi cut-out, 42 psi differential.
Operating pressures: High, 170 to 200 psi. Low, 30 to 37 
psi.
In attempting to adjust the pressure control, you can 
do damage to your unit by accidentally adjusting the 
differential.  Please make small incremental adjustments 
if a temperature adjustment is necessary, please contact 
the service department at Delfield (800) 733-8829 #1, 
or your local service agent.  Delfield is not responsible 
for charges incurred while having the pressure control 
adjusted.
CONTROL SETTINGS: 500 CR & OR