Installation Overview
For use with 350-MHz or greater Intel processor-based servers only
Writer: Cheri Stewart   Project: Compaq ProLiant 3000 Servers Setup and Installation Guide   Comments: 179776-002
File Name: C-CH02.DOC   Last Saved On: 1/12/99 3:15 PM
COMPAQ CONFIDENTIAL - NEED TO KNOW REQUIRED
Grounding
For proper operation and safety, this equipment is required to be properly
grounded in accordance with NFPA 70-1993, Article 250. All power
distribution devices, branch wiring, and receptacles must be "Listed" grounding
type devices.
When using power strips for electrical distribution, ensure that ground integrity
is maintained for each connection made. Plug each component into a reliably
grounded outlet.
Server Temperature Requirements
To ensure continued safe and reliable operation of the equipment, locate the
system in a well-ventilated, climate-controlled environment.
The Compaq Maximum Recommended Ambient Operating Temperature
(TMRA) for most server products is 35°C (95°F). Therefore, the temperature in
the room where the rack is located should not exceed 35°C (95°F).