AT&T 555-230-894 User Manual

Page of 332
9-26
Issue 1  September 1995  
Installation
Install queue warning indicator as follows:
1.
Determine port assignment for queue warning indicator from Hunt 
Group Form:
2.
Install patch cord/jumper wires at cross-connect field.
3.
Mount indicator at specified location.
4.
Connect a 2-pair line cord (modular plug at one end) from the 
information outlet to the indicator. See Figure 9-3.
5.
Connect red (R) and green (T) leads to the indicator.
6.
Administer per 
DEFINITY Communications System Generic 3 V2 
Implementation
, 555-230-655.
Install the 1145B1 Power Supply
The 1145B1 closet power arrangement provides an uninterruptible -48VDC 
power source with battery and 1145B1 distribution unit for Integrated Services 
Digital Network (ISDN)/digital communications protocol terminal equipment, 
terminal adjuncts, and other customer provided equipment. During AC power 
interruptions, batteries automatically provide continuous power to the load.
During normal operation, the power supply/charger provides DC power to the 
load via the distribution unit while maintaining the battery in a fully charged 
condition. A manual switch on the distribution unit allows the user to redirect 
reserve power to outputs 1 through 8 or 1 through 32, 
with the switch set to the 1 
through 32 setting, all outputs will be provided battery reserve power.
The 1145B1/1146B1 is a -48V power supply with 200 watt total output. This unit 
is a 110-type distribution unit with 32 output circuits. Each output is current 
limited by a positive temperature coefficient thermistor (PTC). The thermistor 
limits the maximum output to 12 watts and prevents excessive current from 
causing hazards. If the thermistor is current limiting, there is a short across the 
power pair. Each 1145B1 output has an individual light emitting diode to 
indicate the status of the thermistor. If the light emitting diode is on, the 
thermistor has a short on that power pair.
Not all outputs can simultaneously provide 12 watts. The average power per 
output cannot exceed 6.25 watts (200/32 = 6.25). 
The 1145B1 is designed to 
power one integrated services digital network terminal or digital communications 
protocol adjunct per output. The maximum number of terminals or adjuncts is 
EXAMPLE:   Port Number
2
B
02
01
Cabinet
Carrier
Slot
Circuit