Connect System Cabinet Grounds
Issue 1  September 1995 
4-3
Connect System Cabinet Grounds
To connect ground, refer to Figure 4-2 on page 4-4 and perform the following:
1. At lower left rear of the Processor Port Network (PPN) cabinet (Control 
Cabinet A), connect a 6 AWG ground wire to the cabinet ground block. 
See Ap pendix F for international wire conversions for outside North 
America.
NOTE:
A screwdriver is required to loosen and tighten the screws securing 
the ground wire to the ground block.
2. Run the ground wire to an approved ground. Refer to Appendix A.
3. At the Expansion Port Network (EPN) cabinet(s) (as provided), connect a 
6 AWG ground wire to the A-c abinet ground block. 
4. Run the ground wire from the Expansion Port Network (EPN) to the 
Processor Port Network (PPN) cabinet and connect it to the cabinet 
ground block.
NOTE:
If the Expansion Port  Network (EPN) cabinet is remotely located 
from the Processor Port Network (PPN) cabinet (in a separate room 
or building), run the 6 AWG cabinet ground wire to an approved 
protective ground.
5. At the Processor Port Network (PPN) cabinet, connect a 10-AWG wire to 
the cabinet ground block. At a later time, tie-wrap the ground wire 
(coupled bonding conductor) to the trunk cables, terminating it at the 
coupled bonding conductor terminal bar at the cross-connect field for the 
switch. Refer to Figure 4-9 on page 4-13 for an illustration of the coupled 
bonding conductor.