Install and Connect the Cabinets
4-6
Issue 1  September 1995 
Connect Power
Connect either AC or DC power as described in this section.
Verify the label near the circuit breaker on the power supply toward the rear of 
each cabinet corresponds to your local voltage type.
!
DANGER:
If the label is different than the voltage type at your site, notify your A T & T 
representative immediately for a replacement power supply. Do not, under 
any circumstances, connect to power!
Connect AC Power
Figure 4-2 applies to multiple Processor Port Networks (PPN) and Expansion 
Port Network (EPN) cabinet arrangements. If multiple Expansion Port Network 
(EPN) cabinets are required, you must provide the receptacles for the 4-cabinet 
Processor Port Network (PPN) arrangement in addition to the receptacles for a 
2-, 3-, or 4-cabinet Expansion Port  Network (EPN) arrangement. Provide one 
receptacle per single-carrier cabinet.
1. Verify the circuit breakers are OFF .
2. Connect cabinet AC line cords to the AC power receptacles. The AC line 
cords for the cabinets must first be connected to the cabinets and then to 
the AC power receptacles.
Connect DC Power
The following procedures apply to both the Processor Port Networks (PPN) and 
Expansion Port Networks (EPN).
Figure 4-4 shows a typical power and grounding layout for a DC-powered 
single-carrier cabinet. The size of the wire required for the -48 VDC and -48 volt 
return must ensure the -48 VDC supplied by the battery plant to the cabinets will 
be maintained between -42.5 and -52.5 volt DC. This ensures proper operation 
and prevents hardware damage.