Schneider Electric 3.0A User Manual

Page of 40
48049-136-05 
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012
Section 1—General Information
© 1999–2012 Schneider Electric All Rights Reserved
9-EN
EN
G
L
ISH
Zone-Selective Interlocking
Short-time and ground-fault protection can be 
interlocked to provide zone-selective 
interlocking.
Control wiring links several trip units in the 
distribution network and in the event of a fault, a 
trip unit will obey the set delay time only if 
receiving a signal from a downstream trip unit. 
If the trip unit does not receive a signal, tripping 
will be instantaneous (with no intentional delay).
The fault is cleared instantaneously by the 
nearest upstream circuit breaker.
Thermal stresses (I
2
t) in the network are 
minimized without any effect on the correct 
time delay coordination of the installation.
NOTE: Use I
2
t off with ZSI for proper coordination. Using I
2
t on with ZSI is 
not recommended as the delay in the upstream device receiving a restraint 
signal could result in the trip unit tripping in a time shorter than the published 
trip curve.
NOTE: Setting short-time delay (tsd) or ground-fault delay (tg) to the 0 
setting will eliminate selectivity for that circuit breaker.
Figure 6 shows circuit breakers 1 and 2 zone-
selective interlocked.
A fault at A is seen by circuit breakers 1 and 
2. Circuit breaker 2 trips instantaneously and 
also informs circuit breaker 1 to obey set 
delay times. Thus, circuit breaker 2 trips and 
clears the fault. Circuit breaker 1 does not 
trip.
A fault at B is seen by circuit breaker 1. 
Circuit breaker 1 trips instantaneously since 
it did not receive a signal from the 
downstream circuit breaker 2. Circuit breaker 
1 trips and clears the fault. Circuit breaker 2 
does not trip.
Figure 6:
Zone-Selective Interlocking
06133
376
1
2
B
A