Schneider Electric 3.0A User Manual

Page of 40
48049-136-05 
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012
Section 1—General Information
© 1999–2012 Schneider Electric All Rights Reserved
11-EN
EN
G
L
ISH
Short-Time Protection
Short-time protection protects equipment 
against short circuits.
Short-time protection is standard on 2.0A, 
5.0A and 6.0A trip units. It is not available on 
3.0A trip units.
Short-time protection is based on the long-
time pickup (Ir).
The short-time pickup (Isd) (A) sets current 
level (below instantaneous trip level) at 
which circuit breaker will trip after the preset 
time delay.
The short-time delay (tsd) (B) sets the length 
of time that the circuit breaker will carry an 
overcurrent above the short-time pickup 
current level before tripping. It is adjustable 
on the 5.0A and 6.0A trip unit and factory set 
to zero on the 2.0A trip unit.
The I
2
t on/I
2
t off option provides improved 
selectivity with downstream protective 
devices:
— With  I
2
t off selected, fixed time delay is 
provided.
— With  I
2
t on selected, inverse time I
2
t
protection is provided up to 10 x Ir. 
Above 10 x Ir, fixed time delay is 
provided.
Intermittent currents in the short-time tripping 
range which do not last sufficiently long to 
trigger a trip are accumulated and shorten 
the trip delay appropriately.
Short-time protection can be zone-selective 
interlocked (ZSI) with upstream or 
downstream circuit breakers. 
Setting tsd to the 0 setting turns off zone-
selective interlocking.
Short-time protection uses true RMS 
measurement.
Short-time pickup and delay can be adjusted 
to provide selectivity with upstream or 
downstream circuit breakers.
Figure 8:
Short-Time Protection Switches
Table 2:
Micrologic Trip Unit Short-Time Delay Values
Setting
Short-Time Delay
I
2
t off (Isd at 10 Ir) (seconds)
0
0.1
0.2
0.3
0.4
I
2
t on (Isd at 10 Ir) (seconds)
0.1
0.2
0.3
0.4
tsd (min. trip) (milliseconds)
20
80
140
230
350
tsd (max. trip) (milliseconds)
80
140
200
320
500
NOTE: Use I
2
t off with ZSI for proper coordination. Using I
2
t on with ZSI is 
not recommended as the delay in the upstream device receiving a restraint 
signal could result in the trip unit tripping in a time shorter than the 
published trip curve.
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i
tsd
(s)
on   
 
I
2
t
.
2
.
3
.
4
.
4
.
1
.
2
.
3
.
1
0
off
instantaneous
long time
alarm
Ir
x In
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
3
4
6
8
10
12
15
off
2
06133204
A
B
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i
tsd
(s)
on   
 
I
2
t
.
2
.
3
.
4
.
4
.
1
.
2
.
3
.
1
0
off
instantaneous
long time
alarm
Ir
x In
ground fault
B
C
D
E
F
G
H
J
Ig
tg
(s)
on   
 
I
2
t
.
2
.
3
.
4
.
4
.
1
.
2
.
3
.
1
0
off
A
.5
1
2
4
8
12
16
20
tr
(s)
@ 6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
3
4
5
8
10
12
15
off
2
test
06133351
A
B
Micrologic 6.0A Trip Unit
Micrologic 5.0A Trip Unit