Schneider Electric 3.0A User Manual

Page of 40
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
 48049-136-05
Section 3—Operation
Rev. 01, 07/2012
© 1999–2012 Schneider Electric All Rights Reserved
24-EN
ENGLISH
Wire circuit breakers for zone-selective 
interlocking.
Figure 34:
ZSI Wiring Example
Communication Module values
If the optional circuit breaker communication 
module (BCM) is installed, use the ammeter to 
set communication module values.
To access the communication module menu:
1. Current menu is displayed.
2. Simultaneously press both menu button and 
scroll button down for three seconds.
3. Communication module addressing menu 
will appear.
Figure 35:
Access Communication Module Menu