Schneider Electric 3.0A User Manual

Page of 40
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
 48049-136-05
Section 3—Operation
Rev. 01, 07/2012
© 1999–2012 Schneider Electric All Rights Reserved
26-EN
ENGLISH
Trip Unit Settings Check
Use the ammeter switch setting menu to check 
the trip unit settings.
1. Press menu button twice.
2. Switch settings menu will appear.
3. Press scroll button to advance to next 
screen.
4. After checking trip unit settings, press menu 
button once to return to main menu.
Table 9:
Trip Unit Settings
Setting
Window
2.0A 3.0A 5.0A 6.0A
Ir
Long-Time 
Pickup
X
X
X
X
tr
Long-Time 
Delay
X
X
X
X
Isd
Short-Time 
Pickup
X
X
X
tsd
Short-Time 
Delay
X
X
Ii
Instantaneous 
Pickup
X
X
X
Ig
Ground-Fault 
Pickup
X
tg
Ground-Fault 
Delay
X
Trip Unit Operation Verification
Use a test kit connected to the trip unit test plug 
receptacle (A) to verify trip unit is functioning as 
desired. See instructions shipped with test kit to 
perform verification tests.
Figure 37:
Verify Trip Unit Operation
  A
Ir=
06133382
menu
06134247
menu
06134247
06134248
s
tr=
06133383
06134248
  A
Isd=
06133384
06134248
s
tsd=
06133385
06134248
Ii=
06133387
 A
06134248
 A
Ig=
06133388
06134248
s
tg=
06133389
06133205
06133218
A