Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012
Section 3—Operation
© 1999–2012 Schneider Electric All Rights Reserved
27-EN
EN
G
L
ISH
Equipment Ground-Fault Trip 
Functions Testing
Paragraph 230-95 (c) of the National Electrical 
Code requires that all equipment ground-fault 
protection systems be tested when first installed. 
With the circuit breaker closed, test the ground-
fault (Micrologic 6.0A trip unit only) trip 
functions. For instructions on how to close circuit 
breaker, refer to the circuit breaker installation 
instructions shipped with the circuit breaker.
1. Press the ground-fault test button (A). Circuit 
breaker should trip.
2. If circuit breaker does not trip, contact the 
local field office.
NOTE: Trip unit must be powered to test ground-fault trip function. The trip 
unit is powered if the circuit breaker is carrying more than 0.20 x In of load 
current, if the 24 Vdc external power supply is connected or if the Full-
Function Test Kit or Hand-Held Test Kit is connected and on.
Figure 38:
Test Equipment Ground-Fault Trip Function
Trip Unit Resetting
When the circuit breaker trips, the fault indicator 
will remain lit until the trip unit is reset.
Press the reset/test button (A) to reset the trip 
unit after trip.
Do not return circuit breaker to service until cause 
of trip is determined. For more information, refer 
to the circuit breaker installation instructions 
shipped with the circuit breaker.
Figure 39:
Reset Trip Unit
Trip Unit Status Check
NOTE: Trip unit must be powered to test battery. The trip unit is powered if 
the circuit breaker is carrying more than 0.20 x In of load current, if the 24 
Vdc external power supply is connected or if the Full-Function Test Kit or 
Hand-Held Test Kit is connected and on.
To check trip unit battery and trip indicators, 
press the test/reset button (A).
All trip indicators (B) will light up
Battery status will be displayed
If no battery status is displayed, there is no 
battery installed. 
The battery bar graph reading is valid after 
the reset button has been released.
If the battery bar graph shows the battery 
needs to be changed, use Square D battery 
catalog number S33593:
— lithium battery
— 1.2AA, 3.6 V, 800 ma/h
For instructions on replacing battery, see 
Section 6—Battery Replacement.