EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
59
74-2958—1
DIRTY FILTER MONITOR
The air filter in the air handler can be monitored by the W7750 
and an alarm issued when the filter media needs replacement. 
The two methods of monitoring the filter are:
1.
A differential pressure switch whose contacts are con-
nected to a digital input on the W7750A or W7750B,C; 
and
2.
A 2-to-10V differential pressure sensor wired to a 
current input on the W7750B,C. If the analog input 
sensor is used, its measured value 0 to 5 inw 
(0 to 1.25 kPa) is compared to a user-selectable 
setpoint (FltrPressStPt—valid range: 0 to 5 inw 
(0 to 1.25 kPa)), and the Dirty Filter alarm is issued 
when the pressure drop across the filter exceeds the 
setpoint.
START-UP
START_UP_WAIT is the first mode after application restart or 
power-up. During START_UP_WAIT, the analog and digital 
inputs are being read for the first time, no control algorithms 
are active, and the physical outputs (fan and heat/cooling 
stages) are in the de-energized position. The node remains in 
the START_UP_WAIT mode for a pseudo-random period 
(depending on neuron_id) between 12 and 22 seconds and 
then transitions to one of the operating modes, depending on 
the inputs that are read from the physical and network inputs. 
The pseudo random period prevents multiple controllers from 
simultaneously starting major electrical loads when power is 
restored to a building. 
NOTES:  After a controller download via Care/E-Vision, the 
delayed reset time is bypassed and the controller 
starts after a 40-second initialization.
Not all network inputs can be received during the 
START_UP_WAIT period because many network 
variables are updated at a slower rate; therefore 
some control decisions can be considered tempo-
rarily inappropriate.
Temperature Control Operations
See Fig. 49 for a diagram of a typical W7750 Unit.
Fig. 49. Schematic diagram for a typical W7750B Unit.
WINDOW CONTACT
OCCUPANCY
SENSOR
M
OA TEMP
FILTER
FAN
COOL
COIL
HEAT
COIL
DA TEMP
RA TEMP
EXCEL 10
W7750
CVAHU
T7770 OR T7560A,B
RETURN
AIR
DISCHARGE
AIR
OUTDOOR
AIR
CEILING
ROOF
-
+
M17488