Vulcan-Hart SCB47 User Manual

Page of 8
 
5
 - 
Purge the supply line to clean out any dust, dirt, or any foreign matter before connecting 
the line to the unit. 
Codes require that a gas shut-off valve be installed in the gas line ahead of the 
charbroiler.  The gas supply line must be at least the equivalent of ¾” iron pipe.  72-inch 
units should be connected to the gas supply on both the left and right sides to provide 
adequate gas flow.   
A pressure regulator is supplied and must be installed outside of the broiler when making 
the gas supply connection.  Standard orifices are set for 5"WC (Water Column) for 
Natural Gas — 10"WC (Water Column) for Propane.  Use the 
1
/
8
” pipe tap on the burner 
manifold for checking pressure.  Make sure the gas piping is clean and free of 
obstructions, dirt, and piping compound. 
An adequate gas supply is necessary.  Undersized or low pressure lines will restrict the 
volume of gas required for satisfactory performance.  A minimum supply pressure of 7" 
W.C. for natural gas and 11" W.C. for propane gas is recommended.  With all units 
operating simultaneously, the manifold pressure on all units should not show any 
appreciable drop.   
When testing the gas supply piping system, if test pressures exceed ½ psig (3.45 kPa), 
the charbroiler and its individual shutoff valve must be disconnected from the gas supply 
piping system.  When test pressures are ½ psig (3.45 kPa) or less, the charbroiler must 
be isolated from the gas supply piping system by closing its individual manual shut-off 
valve during any pressure testing of the system. 
WARNING:  PRIOR TO LIGHTING, CHECK ALL JOINTS IN THE GAS SUPPLY LINE FOR 
LEAKS.  USE SOAP AND WATER SOLUTION.  DO NOT USE AN OPEN FLAME. 
 
GAS PRESSURE REGULATOR INSTALLATION 
Gas regulator pressure is preset at 5” Water Column (W.C.) for natural gas, and 10” W.C. 
for propane gas. Minor adjustments may be required based on site specific gas pressure. 
Install the regulator as close to the broiler on the gas supply line as possible. Make sure 
that the arrow on the underside of the regulator is oriented in the direction of gas flow to 
the broiler (Fig. 2) and the regulator is positioned with the vent plug and adjustment 
screw upright (Fig. 3). 
 
Fig. 2 
 
Fig. 3 
The minimum supply pressure (upstream of the regulator) should be 7-9” W.C. for natural 
gas and 11-12” W.C. for propane gas. At no time should the hotplate be connected to 
supply pressure greater than ½ psig (3.45 kPa) or 14” W.C.