Servicing should only be performed by a Qualifi ed Service Agent
TROUBLESHOOTING
TEST 3: CONTINUITY CHECK OF HIGH LIMIT (ECO)
Conditions:
Power On – No Hot Water
• 
Red, heater control “Call for Heat” LED – on
• 
Red ignition control board diagnostic LED – 4 Flashes
• 
Note LED Flash Code before resetting water heater control.
• 
See 
• 
Ignition Control Board: Error Codes.
Turn Power OFF.
• 
Figure 22
TEST 3
Continuity check of ECO 
(energy cut-off, high limit)
Black to Black wires of upper probe. 
Power is off.
IF.........
Then............
continuity is indicated  
(ZERO “0.0” Resistance)
opens at 203° F; closes at 193° F. If water is below 193° F, continuity is correct.
continuity is not present 
(meter reads “0.L”)
replace ECO sensor if water temperature is below 193° F.
water is less than 120° F
• reset status LED should be on.
• replace heater control if control will not  manually reset.