1.3.1  Reduced clearances using shielding 
 
You  may  decrease  the  minimum  clearances  to  combustible  materials  by  installing  heat  radiation  shields 
between the walls or the ceiling and the stove.  Those heat radiation shields must be installed permanently, 
and must be made of a heat-resistant or heat-tolerant material.  Consult the table below: 
 
 
Reducing Clearances With 
Shielding 
TYPE OF PROTECTION 
Sides and 
Rear/Back 
Top 
Sheet metal, a minimum of 0,013" (0,33 mm) spaced out at 
least 7/8" (21 mm) by non-combustible spacers. 
67% 
50% 
Ceramic tiles, or an equivalent non-combustible material on 
fire-proof supports spaced out at least 7/8" (21 mm) by non-
combustible spacers. 
50% 
33% 
Ceramic tiles, or an equivalent non-combustible material on 
fire-proof  supports  with  a  minimum  of  0,013"  (0,33  mm) 
sheet metal backing spaced out at least 7/8" (21 mm) by non-
combustible spacers. 
67% 
50% 
Brick spaced out at least 7/8" (21 mm) by non-combustible 
spacers. 
50% 
N/A 
Brick with a minimum of 0,013" (0,33 mm) sheet metal 
backing spaced out at least 7/8" (21 mm) by non-
combustible spacers. 
 
67% 
N/A 
Source: CSA Standard B365-1991, Table 4, Page 27