Panasonic 4301 Leaflet

Page of 2
 
All technical features and data are subject to changes without notice, resulting from continuous development and improvement. 
Product Leaflet 
Date of issue 
Revision / Date of revision  
MEW00308 2003-04-24 
2008-09-15 
 
Type number 
4301 
Analog photoelectric smoke detector 
           
+
COM loop
Ext. LED
SA (L)
SA (L)
C
.i
.e
. EBL5
12 
/ EBL
128
C
O
M
 lo
op
 in
p
u
t
SB (C)
SB (C)
SB
SB
E-
E-
SA
SA
E+
E+
Mark
Mark
SB
E-
SAo
E+
Mark
SAi
3312
4313
3312FL/F
 
In the detector: 
See also "Engineering Instructions for detectors Type 430x".
 
SA/SB Contact pins for COM loop / address setting tool 3314 
E+/E-  Contact pins for External LED 
Tl 
Type number label;  Detector type 
Al 
Address label;  For the programmed COM loop address to be written. 
Lsh 
Locking screw hole (prepared for drilling through detector body) 
Ls Locking 
screw 
Prepared for mechanical locking with analog base 3312x / 4313.  One hexagon socket screw 
(Ls) is attached (1.5 mm Hex key to be used).  The 2.5-2.7 mm hole (Lsh) has to be drilled. 
Technical data 
Voltage (V DC) 
   rated 
   allowed 
   normal (on COM loop) 
 
28 
12-30 
24 
Current consumption at nom. volt. 
from COM loop (mA) 
   quiescent 
   active (incl. internal LED) 
   ext. LED (connected via base 3312) 
 
 
0.3 
2.3 
max. 2  
Ambient temperature (
°C) 
  operating 
  storage 
 
-10 to +50 
-25 to +75 
Ambient humidity (% RH) 
max. 95, non condensing 
Ingress Protection rating (estimated) 
IP 51 
Sensitivity (obscuration; %/m) 
 
  NORMAL mode 
  2330 mode 
  2312 mode 
Depending on the mode.  
 
3.6 / 3.0 / 2.4   (Low / Normal / High) 
3.5   (Normal) 
2.6 
Size 
∅ x h (mm) 
102 x 36 
Weight (g) 
68 
Construction / Colour 
Modified polycarbonate / Grey (N8, Munsell colour code) 
Approvals 
 05  EC Certificate no. 0786-CPD-20144, EN54-7 
 
SB
SA 
E- 
E+ 
Tl 
Ls 
Lsh 
Al 
The detector is plugged in the analog base 3312x / 4313. 
The COM loop / Ext. LED are connected to the analog base.