Bosch FMR-1000-RCMD User Manual

Page of 44
Remote Command Center
 Operating | en
13
Bosch Security Systems, Inc.
Installation and Operation Guide
F.01U.078.098 | 3.0 | 2011.11
Table 9.1
LED Operation
Display
The FMR-1000-RCMD Remote Command Center uses an 80-character (4 lines x 20 characters) 
wide viewing-angle LCD display. The display includes a long-life LED backlight. The backlight 
is controlled by the panel, or locally turned on upon any key press and turned off after 
30-second time-out without key press. Even when AC power is lost, the LED backlight remains 
lit if a user is operating the keypad.
Piezo Sounder
The FMR-1000-RCMD Remote Command Center has a piezo that provides audible indication 
of the system status. Refer to Table 9.2 for piezo modes when FMR-1000-RCMD is controlled 
by the panel:
Table 9.2
Piezo Operation with FMR-1000-RCMD Panel Controlled
In case of multiple piezo activation, the system status with highest priority is indicated.
If the Remote Command Center is not controlled by the panel or during a communication 
fault, refer to Table 9.3 for piezo modes:
Table 9.3
Piezo Operation with FMR-1000-RCMD Controlled Locally
Trouble
Yellow
On
When the panel is initializing
When the panel registers a trouble condition from a point, or the panel
When inputs or outputs or other elements are bypassed
Flashing 
1)
When the panel is not operating
When walk test is in progress
Off
When no trouble condition exists
When the panel is resetting
1)
 LED flash rate is 1 Hz (0.5 s on, 0.5 s off).
LED
System Status
Piezo Operation
System Status
Silent
The panel is in a normal state (no alarm, supervisory or trouble 
condition). The panel was silenced or acknowledged after an off-
normal condition.
Continuous beep
The panel is in fire alarm condition.
Periodic beep 
(0.5 s every 2 s)
The panel is in gas alarm condition.
Periodic beep 
(0.5 s every 4 s)
The panel is in supervisory condition.
Periodic beep 
(0.5 s every 10 s)
The panel is in trouble condition or a communication fault exists 
on the Option Bus.
Short beep
With every valid key press.
Piezo Operation
System Status with FMR-1000-RA Controlled Locally
Periodic beep 
(0.5 s every 10 s)