Bosch FMR-1000-RCMD User Manual

Page of 44
Remote Command Center
 Troubleshooting | en
15
Bosch Security Systems, Inc.
Installation and Operation Guide
F.01U.078.098 | 3.0 | 2011.11
pattern, or they fully de-energize, as defined by the global option “Silence Config”. Strobes 
continue flashing.
If programmed, the panel transmits a silence report to the central station.
If the panel is already silenced, pressing [SILENCE] again causes an unsilence command in the 
panel. Silence operation does not reset the alarm status and does not return the activated 
input to normal service. Any new alarm reactivates any silenced outputs.
Trouble Reminder
If any events are not cleared within 24 hours after the [SILENCE] or [ACK] key was pressed, 
the panel turns on the piezo again and events are transmitted to the central station again.
Reset
Pressing the reset key turns off the piezo and all activated or silenced outputs. The reset 
operation  turns off auxiliary power AUX/RST for 5 seconds, and activates the global resetting 
zone. All alarms, supervisories, and troubles caused by activation of SLC points are cleared. 
Then the panel tries to reset all points that are in off-normal status. Not all system trouble 
conditions are affected by the reset operation. If programmed, the panel transmits a reset 
report to the central station.
Any alarm or trouble that exists after a reset causes the system to sound again.
Drill
To activate the drill operation, the [DRILL] key must be pressed twice to prevent accidental 
activation. Pressing the key once the system prompts for confirmation. Pressing the [DRILL] 
key again turns on all unbypassed NACs and drillable relay outputs.
The drill operation stops if the reset key is pressed, or it is automatically cancelled if the 
operation was started for a programmed time. A system reset is automatically performed by 
stopping the drill so that the panel and all field devices restore to their normal operation.
If programmed, a drill start report and a drill stop report are transmitted to the central 
station.
10
Troubleshooting
11
Specifications
11.1
Electrical
Display
LED
Piezo
Description
NOT PROGRAMMED
0.5 s on/
0.5 s off
0.5 s every 
10 s
No communication activities on 
the device address.
NO COMMUNICATION
0.5 s on/
0.5 s off
0.5 s every 
10 s
After 60 seconds of no 
communication activities on any 
Option Bus address.
COMMUNICATION OK
off
off
Communication on the device 
address; no text received yet.
Operating voltage
Nominal 12 V DC or 24 V DC/FWR
Current consumption at 12 V DC
Standby current
25 mA maximum (only Power LED on)
Alarm current
150 mA maximum (with annunciator lit and piezo 
on)