Vulcan-Hart BVD36FP52(F,L)N-1 User Manual

Page of 40
Page 34
19400-3-0406
CAUTION: ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL 
LOCAL, CITY AND STATE BUILDING CODES. BEFORE MAKING THE ELECTRICAL CONNECTION, MAKE SURE THAT 
MAIN POWER SUPPLY IS DISCONNECTED. THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN  
ACCORDANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL 
CODE ANSI/NFPA 70 (LATEST EDITION)
.
A  factory  installed  junction  box  is  located  on  the  lower 
right  side  of  the  fireplace.  Wiring  must  be  fed  to  the 
junction box and attached to the receptacle that is provided. 
Leave  approximately  6"  of  wire  in  the  junction  box  for 
connection.
Attach black wire to one side of the receptacle and white 
wire to opposite side of receptacle. The ground wire should 
be attached to the green (ground) screw.
Install  the  receptacle  into  the  junction  box. Attach  cover 
plate.
Figure 28
STANDARD MILLIVOLT VALVE MODELS
120V DIRECT IGNITION VALVE MODELS
1.  To wire Junction Box Receptacle, remove the tab on the side of 
the receptacle (hot side) to split receptacle. This will be required 
to separate blower and valve circuits.
2.  Power for switched and live sides of Duplex Receptacle must come 
from the same power source. (One circuit breaker on main panel 
must switch all power off.)
3.  From the wall box to the fireplace a 3-wire conductor with ground is 
recommended, however (2) two-wire conductors with grounds may 
be used in place of a 3-wire conductor with a ground if the black 
wires from the thermostat and blower switch are identified. 
4.  Two wall switches, or a wall switch and thermostat may be used 
to activate the two receptacle plugs independently.
Figure 29
JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS