Desa SBJ18VNA User Manual

Page of 32
www.desatech.com
114744-01B
15
  WARNING:  Use  pipe  joint 
sealant that is resistant to liquid 
petroleum (LP) gas. 
We recommend that you install a sediment trap 
in supply line as shown in Figure 14, page 14, 
depending on your model. Locate sediment trap 
where it is within reach for cleaning. Install in 
piping system between fuel supply and heater. 
Locate sediment trap where trapped matter is not 
likely to freeze. A sediment trap traps moisture and 
contaminants. This keeps them from going into 
heater controls. If sediment trap is not installed or 
is installed wrong, heater may not run properly.
 CAUTION: Avoid damage to 
gas  control.  Hold  gas  control 
with wrench when connecting it 
to gas piping and/or fittings.
CHECKING GAS CONNECTIONS
 WARNING: Test all gas piping 
and connections for leaks after 
installing or servicing. Correct 
all leaks at once.
  WARNING:  Never  use  an 
open flame to check for a leak. 
Apply a noncorrosive leak detec-
tion fluid to all joints. Bubbles 
forming show a leak. Correct all 
leaks at once.
  CAUTION:  Make  sure  ex-
ternal  regulator  has  been  in-
stalled  between  propane/LP 
supply  and  heater.  See  guide-
lines under Connecting to Gas 
Supply, page 13.
PRESSURE TESTING GAS SUPPLY 
PIPING SYSTEM 
Test Pressures In Excess Of 1/2 PSIG 
(3.5 kPa)
1.  Disconnect appliance with its appliance main 
gas  valve  (control  valve)  and  equipment 
shutoff valve from gas supply piping system. 
Pressures in excess of 1/2 psig will damage 
heater regulator.
2.  Cap off open end of gas pipe where equipment 
shutoff valve was connected.
3.  Pressurize  supply  piping  system  by  either 
opening propane/LP supply tank valve for 
propane/LP gas or opening main gas valve 
located on or near gas meter for natural gas 
or using compressed air.
4.  Check all joints of gas supply piping system. 
Apply noncorrosive leak detection fluid to all 
joints. Bubbles forming show a leak. 
5.  Correct all leaks at once.
6.  Reconnect  heater  and  equipment  shutoff 
valve to gas supply. Check reconnected fit-
tings for leaks. 
Test Pressures Equal To or Less Than 
1/2 PSIG (3.5 kPa)
1.  Close equipment shutoff valve (see Figure 15).
2.  Pressurize  supply  piping  system  by  either 
opening propane/LP supply tank valve for 
propane/LP gas or opening main gas valve 
located on or near gas meter for natural gas 
or using compressed air.
3.  Check all joints from gas meter to equipment 
shutoff valve for natural gas or propane/LP 
supply to equipment shutoff valve for pro-
pane/LP (see Figure 16 or 17, page 16). Apply 
noncorrosive leak detection fluid to all joints. 
Bubbles forming show a leak. 
4.  Correct all leaks at once.
INSTALLATION
Continued 
Figure 15 - Equipment Shutoff Valve
Equipment 
Shutoff 
Valve
Open
Closed