Amana medc400 User Manual

Page of 24
13
Determine vent length and elbows needed for best 
drying performance
Use the Vent system chart below to determine type of vent 
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specified in the 
Vent system chart. Exhaust systems longer than those 
specified will:
Shorten the life of the dryer.
Reduce performance, resulting in longer drying times and 
increased energy usage.
The Vent system chart provides venting requirements that will help 
to achieve the best drying performance.
Vent system chart
NOTE: Side and bottom exhaust installations have a 90º turn 
inside the dryer. To determine maximum exhaust length, add one 
90º turn to the chart.
Install Vent System
1. Install exhaust hood. Use caulking compound to seal exterior 
wall opening around exhaust hood.
2. Connect vent to exhaust hood. Vent must fit inside exhaust 
hood. Secure vent to exhaust hood with 4" (102 mm) clamp.
3. Run vent to dryer location. Use the straightest path possible. 
See “Determine vent path” in “Plan Vent System.” Avoid 90º 
turns. Use clamps to seal all joints. Do not use duct tape, 
screws, or other fastening devices that extend into the interior 
of the vent to secure the vent, because they can catch lint.
Install Leveling Legs
1. To protect the floor, use a large, flat piece of cardboard from 
the dryer carton. Place cardboard under the entire back side 
of the dryer. 
2. Firmly grasp the body of the dryer (not the top or console 
panel). Gently lay the dryer on the cardboard. See illustration.
3. Examine the leveling legs. Find the diamond marking. 
4. Screw the legs into the leg holes by hand. Use a wrench to 
finish turning the legs until the diamond marking is no longer 
visible.
5. Place a carton corner post from dryer packaging under each 
of the 2 dryer back corners. Stand the dryer up. Slide the 
dryer on the corner posts until it is close to its final location. 
Leave enough room to connect the exhaust vent.
Level Dryer
Check the levelness of the dryer. Check levelness first side to 
side, then front to back.
If the dryer is not level, prop up the dryer using a wood block. 
Use a wrench to adjust the legs up or down and check again 
for levelness.
Connect Vent
1. Using a 4" (102 mm) clamp, connect vent to exhaust outlet 
in dryer. If connecting to existing vent, make sure the vent is 
clean. The dryer vent must fit over the dryer exhaust outlet 
and inside the exhaust hood. Check that the vent is secured 
to exhaust hood with a 4" (102 mm) clamp.
2. Move dryer into its final location. Do not crush or kink vent.
3. (On gas models) Check that there are no kinks in the flexible 
gas line.
4. Once the exhaust vent connection is made, remove the corner 
posts and cardboard.
Number of 
90º turns 
or elbows
Type of
vent
Box or 
louvered 
hoods
Angled
hoods
0
Rigid metal
64 ft (20 m)
58 ft (17.7 m)
1
Rigid metal
54 ft (16.5 m) 
48 ft (14.6 m)
2
Rigid metal
44 ft (13.4 m)
38 ft (11.6 m)
3
Rigid metal
35 ft (10.7 m)
29 ft (8.8 m)
4
Rigid metal
27 ft (8.2 m)
21 ft (6.4 m)
WARNING
Excessive Weight Hazard
Use two or more people to move and install dryer.
Failure to do so can result in back or other injury.