Hisense kf-34gwe User Guide
5.Air purging
Air and moisture remaining in the refrigerant system have undesirable
effects as indicated below. Therefore, they must be purged completely.
·pressure in the system rises
·operating current rises
·cooling efficiency drops
·moisture in the air may freeze and block capillary tubing
·water may lead to corrosion of parts in the refrigerant system
5-1.Air Purging with a Vacuum Pump (for Test Run)
(1)Check that each tube (both narrow and wide tubes between the indoor
effects as indicated below. Therefore, they must be purged completely.
·pressure in the system rises
·operating current rises
·cooling efficiency drops
·moisture in the air may freeze and block capillary tubing
·water may lead to corrosion of parts in the refrigerant system
5-1.Air Purging with a Vacuum Pump (for Test Run)
(1)Check that each tube (both narrow and wide tubes between the indoor
and outdoor units have been properly connected and all wiring for the
test run has been completed. Note that both narrow and wide tube
service valves on the outdoor unit are kept closed at this stage.
test run has been completed. Note that both narrow and wide tube
service valves on the outdoor unit are kept closed at this stage.
(2)Using an adjustable wrench or box wrench, remove the valve caps from
the service valve on both narrow and wide tubes.
(3) Connect a vacuum pump and a manifold valve (with pressure gauges) to
the service port on the wide tube service valve.(Fig.A)
(4)With the “Lo”knob of the manifold valve open, run the vacuum pump.
The operation time for the vacuum pump varies with tubing length and
the capacity of the pump. The following table shows the amount of time
the capacity of the pump. The following table shows the amount of time
CAUTION
Be su r e t o us e a m a n i f o l d v alve fo r a ir pu r g i ng.
I f i t i s not ava i l a b l e , use a s t o p v alve for
this p u r p ose. T h e “ H i” k n o b of t h e manif o l d
valve mu s t a lwa y s b e kep t c losed.
I f i t i s not ava i l a b l e , use a s t o p v alve for
this p u r p ose. T h e “ H i” k n o b of t h e manif o l d
valve mu s t a lwa y s b e kep t c losed.
Lo
Hi
Indoor unit
Outdoor unit
Fig.A
Manifold valve
Pressure
gauge
Vacuum pump
Table
Required time for evacuation when capacity
of 100 liter/h vacuum pump is used
If tubing length is less than 10 m
10 min. or more
15 min. or more
If tubing length is more than 10 m
Appendix: Installation
90 (1/4 turn)
Narrow tube
Hex wrench
Wide tube
Valve cap
Vacuum hose to manifold valve
Fig.B
The required time in the above table is calculated based on the
assumption that the ideal (or target) vacuum condition is around 10
mmHg abs.
(5) With the vacuum pump still running, close the “Lo”knob of the
manifold valve. Then stop the vacuum pump.
(6)With the accessory hex wrench, turn the valve stem on the narrow
tube service valve counterclockwise by 90 degrees (1/4 turn) for
10 seconds, and then turn the stem clockwise to close it again.
10 seconds, and then turn the stem clockwise to close it again.
(Fig.B)
NOTE
NOTE
CAUTION
Be sure to completely insert the hex wrench
before attempting to turn the valve.
before attempting to turn the valve.
24