Hisense kf-34gwe User Guide

Page of 28
5.Air purging
Air  and  moisture  remaining  in  the  refrigerant  system  have  undesirable 
effects as indicated below. Therefore, they must be purged completely.
·pressure in the system rises
·operating current rises
·cooling efficiency drops
·moisture in the air may freeze and block capillary tubing
·water may lead to corrosion of parts in the refrigerant system
5-1.Air Purging with a Vacuum Pump (for Test Run)
(1)Check  that  each  tube  (both  narrow  and  wide  tubes  between  the  indoor 
and outdoor units have been properly connected and all wiring for the 
test  run  has  been  completed.  Note  that  both  narrow  and  wide  tube 
service valves on the outdoor unit are kept closed at this stage.
(2)Using an adjustable wrench or box wrench, remove the valve caps from 
the service valve on both narrow and wide tubes.
(3) Connect a vacuum pump and a manifold valve (with pressure gauges) to 
the service port on the wide tube service valve.(Fig.A)
(4)With the “Lo”knob of the manifold valve open, run the vacuum pump. 
The  operation  time  for  the  vacuum  pump  varies  with  tubing  length  and 
the capacity of the pump. The following table shows the amount of time 
CAUTION
Be su r e t o us e a m a n i f o l d v alve fo r a ir pu r g i ng. 
I  f  i t  i s  not  ava i l a b l e ,  use  a  s t o p  v alve  for 
this  p u r p ose.  T h e  “ H i” k n o b  of  t h e  manif o l d 
valve mu s t a lwa y s b e kep t c losed.
Lo        
Hi
Indoor unit
Outdoor unit
Fig.A
Manifold valve
Pressure
gauge
Vacuum pump
Table 
Required time for evacuation when capacity
of 100 liter/h vacuum pump is used
If tubing length is less than 10 m
10 min. or more
15 min. or more
If tubing length is more than 10 m
   
   
   
Appendix: Installation
90 (1/4 turn)
Narrow tube
Hex wrench
Wide tube
Valve cap
Vacuum hose to manifold valve
Fig.B
The  required  time  in  the  above  table  is  calculated  based  on  the 
assumption  that  the  ideal  (or  target)  vacuum  condition  is  around  10 
mmHg abs.
(5) With the vacuum pump still running, close the “Lo”knob of the 
manifold valve. Then stop the vacuum pump.
(6)With the accessory hex wrench, turn the valve stem on the narrow 
tube  service  valve  counterclockwise  by  90  degrees  (1/4  turn)  for 
10  seconds,  and  then  turn  the  stem  clockwise  to  close  it  again. 
(Fig.B) 
NOTE
NOTE
CAUTION
Be  sure  to  completely  insert  the  hex  wrench 
before attempting to turn the valve.
24