Honeywell Electrode Humidifier [with HumidiPRO™ H6062 Digital Humidity Control (HM700A1000)] Installation Guide

Page of 80
HM700A1000
11
33-00118EFS—01
Fig. 16. Primary power connection.
NOTES:
Honeywell requires the use of a GFI circuit on this device to protect the homeowner from electrical shock.
When installed correctly, the green wire should be removed from the drain valve.  The green wire comes pre-installed 
from the factory to protect the homeowner in case of an improper installation or when it is not possible to retrofit a GFI 
circuit. See Fig. 24 for the location of green wire on the drain valve.
Ensure that adequate power is available to carry full humidifier amp draw as indicated on the specification label.
Do not use neutral wire as a ground; connect a dedicated ground to ground termination.
All wiring to be in accordance with national and local electrical codes.
HOT
HOT
GROUND
P
240
120
L1
GROUND
E
X
T
I
N
T
240 VAC (1 PHASE)
120 VAC (1 PHASE)
NEUTRAL
HOT
GROUND
P
240
120
L1
GROUND
NOTE:  CONNECT 120 VAC,
“HOT”, TO L1
(OPTIONAL)
(OPTIONAL)
NOTE:  POWER WIRES 
CAN ALSO BE ROUTED 
THROUGH OPENING IN 
BACK OF CABINET
M35806