Honeywell Electrode Humidifier [with HumidiPRO™ H6062 Digital Humidity Control (HM700A1000)] Installation Guide

Page of 80
HM700A1000
13
33-00118EFS—01
START UP
Installation Check
Before turning on power to the HM700, inspect the installation to ensure that it was carried out correctly. 
Fig. 19. Installation check.
CAUTION
Equipment Damage Hazard
Do not leave the On/Off/Drain switch in the drain 
position for more than one complete drain cycle. The 
drain valve solenoid may heat up and result in damage 
to the valve and its wiring.
Do not attempt to drain with no water in system.
On/Off
The HM700 is factory-configured to operate as an On/Off 
humidifier. It will run when 24 VAC from terminal 1 is fed back 
into terminal 2 through an On/Off humidistat and other 
security devices in series.
FUSED DISCONNECT
CORRECT VOLTAGE / AMPS /
PHASE PER SPEC LABEL
(OPTIONAL)  
MOUNTING
- UNIT LEVEL
- SCREWS INTO
 STRUCTURAL
 MEMBER 
STEAM LINE
- ADEQUATE SLOPE
- NO RESTRICTIONS
- NO KINKS IN HOSE
- CONDENSATE TRAPS
  ON LONG RUNS 
HUMIDITY CONTROL
IN RETURN DUCT OR
LOCATION WHICH
REPRESENTS HUMIDIFIED
SPACE (NO DRAFTS, NOT
BY DOOR, NOT BY DIFFUSER)
 
1/2 IN. LINE (MINIMUM) TO WITHIN 4 FT (1.2 M). 30-100 PSIG
SPEC LABEL
AIR GAP
P TRAP
WITH 12 IN (30 CM)
MINIMUM DROP 
 
BEND, OR OTHER
OBSTRUCTION 
NOTE:  U OR HUM TERMINALS IN SERIES BETWEEN TERMINALS 1 AND 2 
AIR PROVING
(OPTIONAL)
IN SERIES BETWEEN
TERMINALS 1 AND 2.
JUMPER BETWEEN
TERMINALS 1 AND 8
MUST BE REMOVED.      
2X DUCT HEIGHT
FROM FAN OR 
TRANSITION
10 FEET (3 M) MINIMUM
4 FEET (1219) MINIMUM
2/3 DUCT
HEIGHT
8
(20 CM)
MINIMUM
HIGH LIMIT
ON/OFF
(OPTIONAL)
IN SERIES BETWEEN
TERMINALS 1 AND 2.
JUMPER BETWEEN TERMINALS
1 AND 8 MUST BE REMOVED.
M35807
DRAIN LINE SHOULD BE ROUTED TO ALLOW FREE FLOW OF 
WATER. ENSURE ADEQUATE SLOPE, NO TRAPS, AND NO KINKS.