• For a hub node—Connect the 32DMX-O, 32DMX, or 32DMX-L output port to the 32MUX-O input port. Alternatively,
connect the 40-DMX-C/40-DMX-CE output port to the 40-MUX-C input port.
• For an OADM node—Connect the AD-xC-xx.x drop (TX) port to the AD-xC-xx.x add (RX) port.
Step 3
Physically connect the proper client interface to the correct add and drop ports.
Step 4
Delete the filter connections related to the pass-through connection that is being converted to an add/drop connection:
a) In node view (single-shelf mode) or multishelf view (multishelf mode), click the Provisioning WDM-ANS Internal
Patchcords tabs.
b) Highlight the pass-through connections between ITU-T channel add and drop port filters.
c) Click Delete.
Step 5
Create two new unidirectional OCHNCs (one heading Side B, the other heading Side A) to support the new add/drop
channels. See the "DLP-G105 Provision Optical Channel Network Connections" task in the chapter, "Create Optical
Channel Circuits and Provisionable Patchcords" of the Cisco ONS 15454 DWDM Configuration Guide.
Step 6
As necessary, complete the "NTP-G184 Create a Provisionable Patchcord" procedure in the chapter, "Create Optical
Channel Circuits and Provisionable Patchcords" in the Cisco ONS 15454 DWDM Configuration Guide.
Step 7
As necessary, add an optical attenuator between the channel TX port of the AD-xC-xx.x, 4MD-xx.x, 32DMX-O, 32DMX,
32-DMX-L, or 40-DMX-C/40-DMX-CE card and the DWDM RX port on the TXP, MXP, or OC-N/STM-N ITU-T line
card.
If the channel is coming from a 32DMX-O, the optical power can be adjusted in CTC by modifying the value of
the internal per-channel variable optical attenuator (VOA).
Note
Step 8
(Optional) The following verification steps might be needed for an intermediate node when a pass-through connection is
converted:
a) Verify that the received channels are at the specified power level. See the
CTC, on page 10
for instructions.
b) Verify that the added channels are equalized with the express channels within +/-1 dB.
c) If the channels are not equalized with the express channels within +/-1 dB, check the attenuation of the VOAs.
d) Check all the fiber adapters to minimize their insertion losses. For instructions, see the "NTP-G115 Clean Fiber
Connectors" procedure in the
Stop. You have completed this procedure.
NTP-G87 Change Node Timing Parameters
This procedure changes the timing parameters for the ONS
15454. To switch the timing reference, see the "NTP-G112
Change the Node Timing Reference" procedure in the chapter
"Maintain the Node" of the Cisco ONS 15454 DWDM
Configuration Guide
.
Purpose
None
Tools/Equipment
72