Cisco Model D-PCG1000 PowerKEY CAS Gateway Installation Guide

Page of 178
 
 
Stacking Guidelines 
4004834 Rev D 
21 
 
Considerations When Using Side by Side Equipment Racks 
Often, side-by-side equipment racks will not include an internal wall between them. 
You should take extreme care when installing modulators in these types of systems. 
There is approximately an 18°F (10°C) rise from inlet air temperature to exhaust air 
temperature on a GoQAM. This rise in temperature could have a cumulative effect 
on temperature from one rack to the adjacent one. You must take extreme care not to 
exceed the 122°F (50°C) maximum inlet air temperature requirement in these 
situations. 
 
Considerations When Using Racks with a Wall on One Side 
Rack installations that have the outer wall or side of the rack in place on the exhaust 
side of the GoQAM should note that without sufficient airflow through the rack, the 
heated exhaust air may re-circulate back to the input side of the GoQAM. Depending 
on the situation, this re-circulation air could eventually exceed the specified 122°F 
(50°C) maximum. 
 
Measuring the Inlet Air Temperature 
If you are concerned about inlet air temperature, you should measure the 
temperature of the inlet air in the actual rack as you plan to use it. You should have 
all cabling in place and all adjacent units installed and running. 
Important! Opening the door on the back panel of the rack can have an adverse effect 
on the managed airflow. If access to the door on the back panel is not controlled, you 
should take the inlet air temperature with the back panel door open since, in most 
instances, opening the door will re-direct the airflow in an adverse manner. 
 
Stacking Considerations 
You have two main options for stacking GoQAMs in a rack. The option you choose 
depends on your system requirements. One option is to stack the GoQAMs in a rack 
containing a top-mounted exhaust fan with vented panels on the front and back. The 
second option is to place a top-vented rack over a floor plenum forced air vent. The 
requirements for these two stacking options are described next in this section. 
 
Option 1 – Using a Rack With a Top-Mounted Exhaust Fan 
This stacking option uses a 40 RU configuration containing up to 32 GoQAMs. The 
remaining 8 RUs are configured with 4 RUs at the bottom and 4 RUs at the top. 
The 4 RU space at the bottom is covered with a vented panel on both the front and 
the back. This panel allows air to freely enter the rack to cool the modulators.