Cisco Model D-PCG1000 PowerKEY CAS Gateway Installation Guide

Page of 178
 
 
Stacking Guidelines 
4004834 Rev D 
23 
 
Option 2 – Using a Rack With Floor Plenum Forced Air Cooling 
This stacking option also uses a 40 RU configuration containing up to 32 GoQAMs. 
In Option 2, however, the lower 4 RU space is covered with a solid panel instead of a 
vented one. The upper 4 RU space is vented along with the entire top of the rack. 
The floor plenum forced airflow must also be a minimum of 600 cfm with 2000 cfm 
being the ideal amount. 