4.7
Chassis Ground Connection
Mounting
 the fuse panel on a metal equipment rack using the metal mounting brackets provided
with
 the fuse panel provides a sufficient return path to meet equipment grounding requirements.
However,
 a separate grounding conductor is often required by local practice or local inspectors.
A
 separate chassis grounding conductor is always needed when the fuse panel is mounted to
non-grounded
 or  non-conducting material  such  as  a  plastic  rack  or cabinet.  When  the  panel
requires
 separate chassis grounding, the chassis grounding conductor must be sized to match the
upstream
 protection device feeding the panel. This provides an adequate return path capable of
allowing
 the fuse to fail in the unlikely event of a battery wire to chassis fault.
Connect
 one or both of the chassis ground connectors (labeled C. GND) to the equipment rack
ground
 (see 
 using the following chassis grounding recommendations:
• Chassis
 grounding conductor connection point: Two #10 studs (with nuts) on 0.625 inch
(15.875 mm)
 centers are provided for connecting a grounding conductor to the fuse panel. 
• Chassis
  ground  conductor:  Use  two  #10  AWG  wires  if  using  both  chassis  ground
connectors
 or one #6 AWG wire if using one chassis ground connector. Two #10 crimp
ring
 terminals (for use with #10 AWG wires) are included with the fuse panel.
• Place
  the  ring  terminals  over  the  chassis  grounding  studs  and  tighten  the  stud  nuts  to
approximately
 15 pound-force inches (1.7 Newton meters) of torque. 
• Connect
  the  ground  conductors  to  an  approved  office  ground  source  per  local  code  or
practice.
 
Figure 19. Chassis Ground Connection
USE TWO #10 AWG WIRES IF USING BOTH CHASSIS GROUND CONNECTORS OR ONE #6 AWG WIRE IF USING ONLY ONE
CHASSIS GROUND CONNECTOR.
TWO #10 CRIMP RING TERMINALS FOR ATTACHING THE #10 WIRES TO THE CHASSIS CONNECTORS ARE PROVIDED
 WITH THE FUSE PANEL.
PLACE THE RING TERMINALS OVER THE CHASSIS SCREWS AND TIGHTEN THE NUTS DOWN ON THE TERMINALS. IF NOT
USING TERMINALS, WRAP THE WIRE(S) AROUND THE CHASSIS SCREW(S) AND TIGHTEN THE NUTS DOWN ON THE WIRES.
CONNECT THE WIRE(S) TO THE EQUIPMENT RACK.
GROUND SCREW AND NUT 
GROUND SCREW AND NUT 
16160-A