Troubleshooting 38 
Troubleshooting 
In this section 
LED and audible alarm troubleshooting..................................................................................................... 38 
Battery condition .................................................................................................................................... 39 
Bypass is out of range 
............................................................................................................................ 39 
General alarm condition ......................................................................................................................... 40 
Input voltage is out of range ..................................................................................................
.................. 40 
Insufficient warning of low batteries..........................................................................................
................ 40 
Internal UPS fault condition...................................................................................................
................... 40 
Low battery shutdowns............................................................................................................................ 41 
Overload condition 
................................................................................................................................ 41 
REPO condition.................................................................................................................
..................... 41 
Site wiring condition..........................................................................................................
..................... 41 
UPS does not provide the expected backup time 
........................................................................................ 41 
UPS does not start .................................................................................................................................. 42 
UPS frequently switches between utility and battery power ......................................................................
.... 42 
UPS is in Auto-Bypass mode .....................................................................................................
............... 42 
UPS is on battery..............................................................................................................
...................... 42 
Utility power condition ........................................................................................................
.................... 42 
 
LED and audible alarm troubleshooting 
          
General 
Alarm 
LED 
On 
Battery 
LED 
Battery 
Fault 
LED 
Site 
Wiring 
Fault 
LED 
Utility 
LED 
Overload 
LED 
Audible alarm  Can alarm 
be silenced 
("
Condition 
Off  Off Off Off Green 
Off  No audible 
alarm 
N/A 
UPS is in Operate 
mode (on page 
Off  Off Off Off Flashing 
green 
Off 
No audible 
alarm 
N/A 
UPS is in Standby 
mode (on page 
Off  Off Off Off Red Off  On—1 beep 
every 5 
seconds 
Yes 
UPS is in Auto-Bypass 
mode (on page 
Flashing 
red 
Off Off Off Red Off  On—1 beep 
every 5 
seconds 
Yes 
General alarm 
condition—UPS is in 
Auto-Bypass mode 
("
Off  Off Off Off Flashing 
red 
Off 
On—1 beep 
every 5 
seconds 
Yes 
Bypass is out of range 
(on page