Panasonic cu-4ks24nbu User Manual

Page of 114
Outdoor Unit  :  CU-4KS31NBU
Indoor Unit 
:  CS-MKS9NKU 
×
 4
Power Supply  :  230V Single Phase 60Hz
RATING CAPACITY:   
30,600 BTU/h
      AIR FLOW RATE:
1,036 CFM
INDOOR
OUTDOOR
ENT. TEMP. 
o
F (
o
C)
AMBIENT TEMP. 
o
F (
o
C)
WB
DB
65
75
85
95
105
115
(18.3)
(23.9)
(29.4)
(35.0)
(40.6)
(46.1)
TC
30,850
29,770
28,590
27,980
22,750
16,560
72 (22.2)
SHC
24,260
23,660
23,260
22,860
20,440
16,560
59
76 (24.4)
SHC
27,890
27,280
26,680
26,480
22,750
16,560
(15.0)
80 (26.7)
SHC
30,850
29,770
28,590
27,980
22,750
16,560
84 (28.9)
SHC
30,850
29,770
28,590
27,980
22,750
16,560
88 (31.1)
SHC
30,850
29,770
28,590
27,980
22,750
16,560
TC
32,150
31,030
29,820
29,290
23,300
16,930
72 (22.2)
SHC
20,040
19,640
19,030
18,830
16,420
13,800
63
76 (24.4)
SHC
23,660
23,260
22,660
22,450
19,840
16,930
(17.2)
80 (26.7)
SHC
27,480
26,880
26,480
26,080
23,300
16,930
84 (28.9)
SHC
30,900
30,500
29,820
29,290
23,300
16,930
88 (31.1)
SHC
32,150
31,030
29,820
29,290
23,300
16,930
TC
33,410
32,280
31,030
# 30,600
23,790
17,260
72 (22.2)
SHC
15,820
15,410
15,010
14,810
12,200
9,780
67
76 (24.4)
SHC
19,440
19,030
18,430
18,430
15,820
13,400
(19.4)
80 (26.7)
SHC
23,260
22,660
22,250
22,050
19,440
17,020
84 (28.9)
SHC
26,680
26,280
25,870
25,670
23,060
17,260
88 (31.1)
SHC
30,300
29,900
29,290
29,290
23,790
17,260
TC
34,630
33,470
32,190
31,890
24,200
17,520
72 (22.2)
SHC
11,390
10,990
10,590
10,380
7,770
5,560
71
76 (24.4)
SHC
15,010
14,610
14,210
14,010
11,390
9,180
(21.7)
80 (26.7)
SHC
18,830
18,230
17,830
17,830
15,010
13,000
84 (28.9)
SHC
22,250
21,850
21,450
21,250
18,630
16,420
88 (31.1)
SHC
25,870
25,470
25,070
24,870
22,250
17,520
TC
35,630
34,460
33,160
33,010
24,460
17,680
75
76 (24.4)
SHC
10,790
10,380
9,980
9,780
7,170
5,150
(23.9)
80 (26.7)
SHC
14,410
14,010
13,600
13,600
10,990
8,980
84 (28.9)
SHC
18,030
17,630
17,220
17,220
14,410
12,400
88 (31.1)
SHC
21,650
21,250
20,840
20,640
18,030
16,020
< Cooling Capacity >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
1. Rating conditions (#)  :  Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB
:  Outdoor Ambient Temp. 95 °F (35 °C) DB
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Freeze Prevention Protection during cooling operation into account. 
For this reason, the value may vary from the actual cooling characteristics.
NOTE