Panasonic cu-4ks24nbu User Manual

Page of 114
Outdoor Unit  :  CU-3KS19NBU
Indoor Unit 
:  CS-MKS9NKU × 3
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity (Low Ambient) >
5-3.  Cooling Capacity (Low Ambient)
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
NOTE
 RATING CAPACITY:    18,800 BTU/h
      AIR FLOW RATE:
777 CFM
INDOOR
OUTDOOR
 ENT. TEMP. 
o
F (
o
C)
    AMBIENT TEMP. 
o
F (
o
C)
WB
DB
15
25
35
45
55
(-9.4)
(-3.9)
(1.7)
(7.2)
(12.8)
TC
19,220
19,090
19,080
19,160
19,010
72 (22.2)
SHC
16,390
19,090
16,240
16,390
16,240
59
76 (24.4)
SHC
18,950
19,090
18,950
18,950
18,950
(15.0)
80 (26.7)
SHC
19,220
19,090
19,080
19,160
19,010
84 (28.9)
SHC
19,220
19,090
19,080
19,160
19,010
88 (31.1)
SHC
19,220
19,090
19,080
19,160
19,010
TC
19,620
19,540
19,610
19,780
19,680
72 (22.2)
SHC
13,220
19,540
13,070
13,220
13,220
63
76 (24.4)
SHC
15,780
19,540
15,780
15,940
15,780
(17.2)
80 (26.7)
SHC
18,650
19,540
18,650
18,650
18,650
84 (28.9)
SHC
19,620
19,540
19,610
19,780
19,680
88 (31.1)
SHC
19,620
19,540
19,610
19,780
19,680
TC
19,910
19,890
20,060
20,340
20,320
72 (22.2)
SHC
9,900
19,890
9,900
10,050
10,050
67
76 (24.4)
SHC
12,620
19,890
12,620
12,770
12,770
(19.4)
80 (26.7)
SHC
15,330
19,890
15,480
15,480
15,480
84 (28.9)
SHC
18,050
19,890
18,050
18,200
18,200
88 (31.1)
SHC
19,910
19,890
20,060
20,340
20,320
TC
20,060
20,120
20,400
20,830
20,890
72 (22.2)
SHC
6,430
20,120
6,580
6,730
6,730
71
76 (24.4)
SHC
9,150
20,120
9,300
9,450
9,450
(21.7)
80 (26.7)
SHC
12,010
20,120
12,160
12,310
12,310
84 (28.9)
SHC
14,580
20,120
14,730
14,880
14,880
88 (31.1)
SHC
17,290
20,120
17,440
17,600
17,600
TC
20,040
20,180
20,600
21,180
21,340
75
76 (24.4)
SHC
5,980
20,180
6,130
6,280
6,280
(23.9)
80 (26.7)
SHC
8,690
20,180
8,840
9,000
9,150
84 (28.9)
SHC
11,410
20,180
11,560
11,710
11,710
88 (31.1)
SHC
14,130
20,180
14,280
14,430
14,430
1.
2. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Freeze Prevention Protection during cooling operation into account. 
For this reason, the value may vary from the actual cooling characteristics.
56