7.  FUNCTIONS
7-1.  Explanation of Functions
The numerical values such as temperature, frequency, time and current in parentheses are an example 
of CU-4KS31NBU and the values are different from the other models.
Control/conditions
INITIAL
Breaker is ON.
Power is supplied to the indoor and outdoor unit 
control circuits, however the unit remains stopped.
Positioning of the outdoor unit electric expansion 
valve is performed.
The ON/OFF operation 
button on the remote 
controller is pressed.
If automatic operation mode has been selected 
with the remote controller, operation begins in 
SENSOR DRY, or COOL mode depending 
on the room temperature and 
outdoor temperature at the time operation starts.
Depending on the operational mode, refer to the SENSOR DRY, or COOL item.
This applies in the case of automatic 
COOL operation.
Unit operation
Explanation
NOTE