Panasonic cu-4ks24nbu User Manual

Page of 114
Control/conditions
COOL
The ON/OFF operation 
button on the remote 
controller is pressed.
The room temperature 
has reached the 
desired temperature.
The outdoor unit does not operate for 3 minutes 
even after the breaker is turned ON.
This is in order to stabilize the return of oil to the 
compressor.
The outdoor unit starts.
(Compressor and the outdoor fan start.)
When the frequency reaches    Hz, 
frequency increases are stopped for a period 
of    seconds. (Refer to Table 1.)
If the indoor and outdoor temperatures are high, 
the current peak cut-off activates, stopping 
any increases in frequency.
The frequency then increases.
Operating frequency is stabilized in order to 
maintain a comfortable environment.
The indoor temperature and the desired 
temperature are approximately equal.
The thermostat turns 
ON again. 
After 3 minutes, the outdoor unit begins operating 
automatically.
During these 3 minutes, a pressure balance is 
achieved, allowing the compressor to start 
more easily.
After the thermostat turns ON again, the 
outdoor unit will not operate for 3 minutes, 
even if the room temperature increases 
above the desired temperature.
Operation is restarted 
within 4 hours (only when 
AUTO mode is selected 
with the remote 
controller).
Within 4 hours after operation was stopped, it is 
assumed that there has been no significant 
change in the indoor and outdoor temperatures, 
and the previous conditions (COOL) are stored.
Starts operating in the same operating mode 
(COOL) and with the same temperature 
settings as before operation was stopped.
Operation starts after 4 
hours or more have 
passed.
New operating mode is determined based on 
the temperature conditions at the time the 
ON/OFF operation button is pressed.
Stop
All indicator lamps turn OFF. The indoor and 
outdoor units stop.
Freeze prevention
In order to protect against freezing, the 
compressor stops temporarily, until the 
temperature of the indoor heat exchanger has 
risen.
The thermostat turns
OFF.
The outdoor unit stops. (It does not stop if the
thermostart for another indoor unit is ON.)
Unit operation
Explanation
The operation lamp illuminates.
The indoor fan operates at the set fan speed.
The outdoor unit stops.
When the temperature of the indoor heat 
exchanger drops to approximately 35.6 °F 
or below, the compressor turns OFF, the 
outdoor fan turns OFF, and the indoor fan 
continues operating with no changes.
Approximately 3 minutes later, if the 
temperature of the indoor heat exchanger 
is adove 46.4 °F, the system returns to its 
original conditions.
The frequency is increased at the rate of 0.5 
Hz every 1 seconds.
Frequency control
    (Hz)
(25) Hz
(35) Hz
(45) Hz
(55) Hz
Outdoor air temperature is below 32 °F.
(120) seconds
(60) seconds
(60) seconds
(180) seconds
Table 1
     (senconds)
Outdoor air temperature is 32 °F or higher.
(60) seconds
(30) seconds
(30) seconds
(90) seconds
66