PreVentiVe and scHeduLed 
Maintenance/Parts rePLaceMent
PreVentiVe Maintenance
Toshiba’s 1800 Series of UPS’ have been designed to provide years of trouble-
free operation requiring a minimum of preventive maintenance.
The best preventive measure is to keep the area around the unit, particularly 
the air inlet vents, clean and free of moisture and dust accumulations.  If the 
atmosphere  of  the  installation  site  is  very  dusty,  use  a  vacuum  cleaner  to 
periodically remove dust accumulations from the exterior of the unit, especially 
around  ventilation  openings.    Schedule  authorized  Toshiba  service  centers 
to perform internal parts inspections annually, or call a Toshiba UPS service 
representative at 1-877-867-8773 (outside the U.S. call 713-466-0277).
Note:  Disconnect AC source before servicing
caution
Proper maintenance of the battery system of this unit is essential to 
the safety and reliability of the UPS system. 
Parts rePLaceMent
The following list shows intervals for periodic maintenance and replacement 
of certain UPS parts.
1) 
Batteries:    Replacement  should  be  done  once  every  3  to  5  years  at  a 
minimum.
2) 
cooling Fans:  Replace once every 3 to 4 years. (Fan replacement must 
be done by Toshiba authorized service personnel).
3)  
Battery Fuses:  Replace the battery fuses every 7 years.