Toshiba 1800 User Manual

Page of 52
1800 Series User Manual
8
aPPendix a:  sPeciFications
 
 
 
 
 
 
 
Note 1:  Currently under development, unit specifications may be changed.
Note 2:  Below 79% input voltage unit may begin parallel operation; supplementing input power with 
battery power.  The point at which parallel operation begins is load dependent (for a detailed 
explanation of Parallel Operation see Appendix C: Parallel Operation).
Note 3:  If input frequency is below 50 Hz, the input Voltage must not exceed 103% of rated input 
Voltage.
Note 4:  In BYPASS mode if the Input voltage is below 90% or above 110%, the UPS output will be 
turned off.  (See Appendix D: Bypass Under Voltage/Over Voltage)
Note 5:  The input capacity is computed to include peak battery charging power.
Model Number
UG1A1A015C6TB
 1
UG1A1A020C6TB
1
UG1A1A024C6TB
1
UG1G2L024C6TB
Rated Capacity
1500VA (1.05KW)
2000VA (1.4KW)
2400VA (1.68KW)
2300VA (1.61KW)
Input
Input voltage
Single phase 120VAC, +10% to -40% 
2  
(72VAC to 132 VAC)
Single phase 
208/240VAC, +10% 
to -40%
1
 
(125 VAC to 229VAC)
Input transformer
Isolation Transformer
Auto Transformer
Input frequency
50/60 Hz +/- 3 Hz 
3
Input capacity 
5
1750VA
2250VA
2650VA
2600VA
Input power factor
Approximately unity (0.95 to 1.0)
Bypass
Input voltage
Single phase 120VAC, +10% to -10% 
4
Single phase 
208/240 VAC  +/- 10% 
4
Output voltage
Single phase 120VAC
Single phase 
208/240/120 VAC
Overload rating
125% for 10 minutes, 150% for 5 minutes
Output
Output voltage
Single phase 120 VAC
Single phase
240/208 /120 VAC
Output transformer
None
Isolation Transformer
Output voltage regulation
Within +/- 3%, steady state
Rated output current (rms)
12.5A
16.6A
20A
9.5A
Maximun output current 
(peak)
31.25Apk
41.5Apk
50Apk
23.75Apk
Inverter overload capacity
125% for 60 seconds, 150% for 30 seconds
Crest factor
2.5 at full load
Output frequency
50/60 Hz (+/- 0.5% in free running mode, line sync range +/-1Hz)
Output voltage waveform
Computer-grade sine wave with less than 3.0% total harmonic distortion with linear load
Rated load power factor
0.7
Effeciency (AC-DC-AC)
80%
80%
80%
79%