aPPendix c:  ParaLLeL oPeration
The 1800 Series UPS offers a standard feature that allows the unit to operate 
with very low input voltage without de-rating the output power.  If the input 
voltage  drops  below  a  certain  point  the  unit  will  switch  to  parallel  mode.  
Parallel  mode  means  that  the  unit  is  using  the  available  input  voltage  and 
supplementing with battery power.  Because battery power is being used, the 
time the unit can operate in parallel mode is limited.  However, the time will be 
longer than that available when the unit is operating on battery power alone.  
The point when the UPS will enter parallel mode will vary depending on the 
output load.  The following graph illustrates the UPS’ transition from battery 
to  line  power  as  the  line  voltage  increases  from  40%  to  100%  of  normal.  
Transition curves are shown for 75% and 100% output load.
 
As shown in the graph, the lower the output load, the lower the input voltage 
can go before parallel mode is activated.  However, the minimum input voltage 
will always remain at 60% (72 VAC for a 120 VAC system).
input Power (%)
input Voltage (%)
% Load
100% Load
Battery
ac input
100
Parallell running:  input Power vs. input Voltage
8
0
0
80
0
20
0
0
120