aPPendix d:  ByPass underVoLtaGe / 
oVerVoLtaGe
When the 1800 Series UPS is in bypass mode the undervoltage and overvoltage 
limits are restricted to +/-10% of the rated input voltage.  If the input voltage is 
outside of this voltage window the UPS output will be turned off.  There is a 5% 
hysteresis associated with both the upper and lower limits.  This means that 
once output has been turned off the input voltage will have to be within ±5% of 
the rated input voltage before the startup sequence will re-initialize. 
When the UPS is started, if the RUN/STOP switch is in the STOP (bypass) 
position the unit will start in the on-line mode for 1 second before switching 
to bypass mode.  If the input voltage is out of range the UPS will turn off the 
output after 1 second rather than switching to bypass.