Digital output function: Select one of the following: 
 
Totalization pulse output: 
Pulse rate 
Max.   3kHz(3000pps) ・・・ DO1 
                Max. 100Hz(  100pps) ・・・ DO2 (option) 
Pulse width 
Can be set within a range of 0.3 to 500ms. 
However, must be 40% or less of the full-scale cycle. 
If the full scale 1000pps is exceeded, 
automatically set to 40% of the full-scale cycle. 
  Multi-range switching output:  In the case of fourfold range or forward/reverse 
double range, you need to add digital output 
optionally. 
  High and low alarm output 
  High-high and low-low alarm output 
  Empty alarm output 
  Preset counter output 
  Converter malfunction alarm output 
  Multiple range high and low limit alarm output (option) 
Output display: Full-dot matrix 128 x 128-dot LCD (with back light) 
 
Communication signal 
Method (protocol):  HART or PROFIBUS (option) 
Load resistance: 
240 to 750Ω (HART) 
Load capacity: 
0.25μF or less (HART) 
 
 
Structure 
  IP67 and NEMA 4X   
Housing 
Aluminum alloy 
Coating   
Acrylic resin-baked coating, pearl-gray colored 
Cable connection port   
1/2-14NPT thread 
Cable connections not provided. 
 
Surge arresters 
  Surge arresters are installed in the power supply and current signal output circuit.