5.3 Notes on Wiring 
Notes on Instrumentation-Converter Wiring 
•  To avoid 2-point grounding, ground the shield of output cable basically at the receiving side. 
•  Use a grounding wire of IV wire 5.5mm
or more. The size of the external grounding terminal screws is M4. 
Do not share a grounding wire with other instruments where grounding current may flow. (An 
independent grounding is preferable.)
 
•  Power cable 
When a 3-core cable is used: Ground with the FG terminal. 
When a 2-core cable is used: Use an external grounding terminal and make the cable as short as possible.