Note: The setting item for the third unit (flow volume direction code) changes       
cyclically as shown below. 
 
   B(bi-directional)    F(forward direction fixed)   R(reverse direction fixed) 
                                      D(difference flow rate) 
 
For Display 2 setting, select DSPL2 from the setting menu. 
 
8.2.7 Custom Coefficient Setting 
 
You can set the custom coefficient used when CUSTOM is selected for display setting or span setting. 
Custom coefficient can be set except 0. 
Displayed value when CUSTOM is set  =  Measured value in m
3
/min unit × Custom coefficient 
Span value when CUSTOM is set          =  Span value in m
3
/min unit × Custom coefficient 
 
Note: Custom coefficient is applied when CUSTOM is selected in the display setting or span setting. 
Other values such as instantaneous flow rate (display unit, such as m/s and m
3
/min
), displayed 
values such as totalized flow and pulse out will not be applied. The details see 10.10 “Custom 
unit function”
 
The following is an example to change the custom coefficient from 1.00 to 2.25. 
Switch operation 
Display example 
Description 
 
B:DISPLAY 
1 DSPL1 
2 DSPL2 
3 CS VAL
 
4 CS UNIT 
5 EXIT 
 
 
Select "CS VAL" from the setting item 
selection menu. 
 
STEP1 
 
 
 
CS VAL 
 
   1.00000 
 
 
 
 
 
The currently set custom coefficient 
(1.00000 in this example) appears. 
 
Then push              . 
 
* Pushing      returns you to the setting 
menu. 
 
STEP2 
 
 
 
CS VAL 
 
   
1
.00000 
 
 
 
 
 
The switches at the bottom change. 
(                                        are shown.) 
 
At the same time, the cursor appears. 
 
 
STEP3 
 
 
 
CS VAL 
 
   2.2
5
000 
 
 
 
 
 
Push            to  move  the  cursor  to  the 
desired digit and push       to change the 
number of the digit. 
Repeat this operation to change the value to 
2.25
 
When the value is changed to the desired 
value, push     to set the custom 
coefficient temporarily. 
ESC
ESC 