TROUBLESHOOTING
This section presents various problems a user might encounter. Use this information to deter-
mine whether external factors cause the problem and how to remedy the situation.
1. The Fault LED will illuminate, indicating the UPS detected a problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional load/battery level LED indicators will be illuminated to provide a 
diagnostic aid to the operator, as shown below:
4. Record the LED condition and horn condition. Turn off the 30A AC input circuit breaker 
on the rear of the UPS and restart the UPS based on the Operating Instructions in this 
manual.
If a problem persists, consult your local dealer, Liebert representative or the Liebert World-
wide Support Group—telephone numbers may be found on the back of this manual. Please 
have the UPS model number and serial number available at the time of your inquiry.
Table 2
LED indicators
LED status
Diagnosis
 Audible alarm
All LEDs on
AC input overvoltage
Continuous beep
A, F on
On bypass due to overtemperature condition until the UPS 
cools, then re-transferring load to inverter.
Continuous beep
Or off due to very high temperatures.
D, F on
Battery overvoltage
Continuous beep
E, F on
Battery mode overload 
Half-second beep 
every 1 second
A, D, F on
Inverter output short 
Continuous beep
Line LED 
flashing
Input AC present, but exceeds PFC input requirements 
(> 276 or < 170)
All battery
capacity LEDs
flashing
Battery failure warning
Continuous beep
B, C, F on
EPO shutdown
Continuous beep
Other
Record condition of LEDs and horn. Contact Liebert technical 
support.
Fault
LED
F
A B C D E