Emerson liebert gxt5000r-208 User Manual

Page of 32
 
24
SPECIFICATIONS
MODEL NUMBER
GXT5000R-208
MODEL RATING VA/W
5000 / 3750
DIMENSIONS: inches (mm)
Unit: W x D x H
16.1 x 23.6 x 5.1(410 x 600 x 130)
Shipping: W x D x H
23.2 x 31.1 x 12.8 (590 x 790 x 325)
WEIGHT: lbs (kg)
Unit
41.2 (18.7)
Shipping
53.8 (24.4)
INPUT AC PARAMETERS
Voltage Range
208 VAC Nominal: 176-276 VAC 
Frequency
50/60 Hz, ±5%; Auto Sensing
Input Power Cord
10 ft. attached, w/ NEMA L6-30P
OUTPUT AC PARAMETERS
Output Receptacles
L6-30R (1), L6-20R (1)
Voltage
208 VAC, ±3%
Frequency
50 Hz or 60 Hz
Waveform
Sinewave
Main Mode Overload
151 - 300% for 2 seconds; 
126 - 150% for 10 seconds; 
105 - 125% for 60 seconds with transfer to bypass
DC INPUT PARAMETERS
Voltage
240 VDC Nominal
Recharge Time
8 Hours to 90% capacity after full discharge into 100% load
ENVIRONMENTAL
Operating Temperature
+32°F to +104°F (0°C to +40°C)
Storage Temperature
+5°F to +122°F (-15°C to +50°C)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating
Storage Elevation
50,000 ft. (15,000 m) maximum
Audible Noise
< 55 dBA
AGENCY
Safety
UL 1778, c-UL Listed
RFI/EMI
FCC Part 15, Subpart B, Class A
Transportation
ISTA Procedure 1A